INSTALLATION
SETUP/PHYSICAL INSTALLATION
3 - 4
I-E96-215A
®
SWITCH S4 SETTINGS
Switch S4 sets the QRC operating states (normal mode or diag-
nostic mode), initialization status, configuration lock status,
diagnostic mode test and module address of the QRC. Figure
shows the location of S4. Figure
shows the S4
dipswitch positions and their uses. Table
shows the avail-
able S4 settings. When setting the module address, refer to
Table
for the corresponding dipswitch positions.
NOTE: For INFI 90 dipswitches, OPEN or OFF have the same
meaning.
Figure 3-2. Switch S4
Table 3-2. Switch S4 Settings
Description
Switch Position
1
2
3
4
5
6
7
8
Normal Mode
Normal Operation
0
0
0
0
0
0
0
0
NVRAM Initialization
0
1
0
0
0
0
0
0
Configuration Lockout
0
0
1
0
0
0
0
0
Diagnostic Mode
Group Test
1
0
0
0
0
0
0
0
Switch/LED Test
1
0
0
0
0
0
0
1
ROM2 Test
1
0
0
0
0
0
1
0
ROM1 Test
1
0
0
0
0
0
1
1
RAM Test
1
0
0
0
0
1
0
0
Clock Test
1
0
0
0
0
1
0
1
Hardware Time Test
1
0
0
0
0
1
1
0
Analog Output Test
1
1
0
0
0
0
1
1
1
1
2
3
4
5
8
6
7
OPEN
NORMAL
MODE/
DIAGNOSTIC
MODE
DIAGNOSTIC TEST
MODULE ADDRESS
MSB
LSB
T00031A