Measuring windows of the PortaSonic 9000
35 / 55
UF_PS9000_BA_02_1108
The output is passive.
8.
Parametering of the inputs and outputs
Navigate to the „Input/output setting“ menu as follows:
Select „SETUP“ and afterwards „COMPL SETUP“ in the „Flow 1“ main measuring window. In
the main menu, navigate to „I/O setting“.
8.1 Parametering of the 4-20mA outputs
The PortaSonic 9000 has two 4-20mA outputs. You may allocate different measured
values to these outputs. The outputs are active ex works, i.e. they are voltage fed by
the PortaSonic 9000. It is, however, also possible to feed them by an external
(passive) supply point. In case of an external supply, the voltage range must be
within 10 to 30 V.
If the 4-20mA outputs of the meter are active and if you connect the analogue
outputs of the PortaSonic with an external device which also has active inputs,
severe damages will occur to the PortaSonic and to the external device.
Therefore, before connecting the two devices, make sure that only one
device is active!
The inputs of the PortaSonic 9000 are active (preset).
The inputs of the external device are directly connected with the PortaSonic 9000.
Active
1:
Passive
2:
Passive
3:
PortaSonic 9000
24V/DC I1/2_A
-
,,
Ri
Ammeter
+
I1/2_B
The output is passive (to be
adjusted in the device).
The output is active
(factory-set)