7-35
Operation & Maintenance Manual
Doc. Ref. MNGRM2CO2 REV. 3
The calibration procedure to be conducted as follows:
1. Open the sensor enclosure and locate Pot VR201 on the sensor PCB. VR201 is used to adjust
the zero point (refer to the picture below).
2. Monitor the output between 0V (negative) and VS (positive).
3. Adjust Pot VR201 to 0V or slightly positive (0.01 V is acceptable).
4. Locate Pot VR202 which is used to calibrate the range (span) of the sensor (refer to the picture
below).
5. Monitor the output between 0V (negative) and VS (positive).
6. Expose the sensor to calibration gas and allow to stabilize (approximately 6 minutes).
7. Adjust pot VR202 to the voltage calculated on the previous page.