CALIBRATION OF BACHARACH MGS.150 NETWORK SENSOR
IMPORTANT:
Failure to test or calibrate the unit in accordance with applicable
instructions and with industry guidelines may result in serious injury or death. The
manufacturer is not liable for any loss, injury, or damage arising from improper
testing, incorrect calibration, or inappropriate use of the unit.
Check local regulations on calibration or testing requirements
The MGS contains sensitive electronic components that can be easily damaged. Do not touch nor
disturb any of these components
The MGS is calibrated at the factory. After installation, a zero adjustment maybe required due to
differences in environmental conditions.
The calibration of the unit must be carried out by a suitably qualified technician, and must be done
in accordance with this manual and in compliance with locally applicable guidelines and
regulations.
Annual checks and gas calibration are recommended. It is also recommended that sensors are
replaced every 3 years or as required. Calibration frequency may be extended based on
application, but should never exceed 2 years.
For improved accuracy and response, the instrument should be zeroed and calibrated in the
environment in which it is being installed.
There are two adjustments required: zero and span. They are monitored at 0V and VS using a 0-5V
scale. If the sensor range is 0-1000 ppm, then 5V=1000 ppm. You will require a multi-meter with clips
to connect to the test pins and a “small flat screwdriver” to adjust the potentiometers.
Parasense offers a calibration kit that consists of a
calibration gas cylinder, a flow regulation valve with
flexible non-absorbent tubing and vented calibration
hood:
Calculating Calibration Voltage:
Sensor outputs are linear. As long as you have a gas cylinder of known concentration you can
calibrate to any desired range.
Example:
For a sensor range of 0-1000 ppm and a cylinder of the target gas at 800 ppm:
So the output voltage signal should be adjusted to 4V.
Summary of Contents for Parasense GRM2 CO2 Series
Page 7: ...1 2 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 GENERAL ARRANGEMENT...
Page 14: ...2 7 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 NETWORK MODULE CONNECTIONS...
Page 74: ......
Page 75: ......
Page 76: ...2 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 GRM2 CO2 CONNECTION SCHEMATICS PS0748...
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ...3 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 ADC 104 GENERAL ARRANGEMENT PM2098...
Page 83: ......
Page 84: ...4 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 ADC 104 PANEL MOUNTING DETAILS PM2247...
Page 85: ......
Page 86: ...5 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 ADC 104 CONNECTION SCHEMATIC PS0753...
Page 87: ......
Page 88: ......
Page 89: ......
Page 91: ......
Page 93: ......
Page 95: ......
Page 96: ......