6-2
Operation & Maintenance Manual
Doc. Ref. MNGRM2CO2 REV. 3
TRAFFIC LIGHT DISPLAY
The traffic light display gives an “at a glance system status” of the monitor. The significance of the
traffic lights is as follows:
Red Flashing Light:
The most recent measurement of refrigerant
concentration has exceeded the ‘Critical’ threshold.
Red Steady Light:
The most recent measurement of refrigerant
concentration has exceeded the ‘Alarm’ threshold.
Amber Flashing Light:
The most recent measurement of refrigerant
concentration has exceeded the ‘Alert’ threshold.
Amber Steady Light:
A measurement of refrigerant exceeding one of the
alarm thresholds has been detected during the last 12
hours.
Green Steady Light:
The refrigerant monitor is operating to design
specification.
Flashing/No Green
Light:
A fault exists on the refrigerant monitor.
ALARM OR FAULT ON THE SYSTEM
If a reading has been detected in excess of the configured alarm thresholds, the traffic light display
will indicate the level of that alarm. The alarm count on the home screen will be incremented, and the
alarm will be logged.
If multiple alarms have been triggered, the traffic lights will indicate the highest alarm level. Individual
alarm information can be obtained from the SAMMs list and Alarms log.
DEFAULT CONFIGURATION SETTINGS
Monitors are supplied programmed with “ready to use” default configuration data. Modifications to
this data can only be carried out through a connected PC running the Parasense configuration
software. Please contact Parasense for more information.
Network Settings
SAMM Settings
IP Address:
192.168.20.168
Alert Level:
3000ppm
Pipe Length:
150m/492ft
Netmask:
255.255.255.0
Alarm Level:
5000ppm
Refrigerant:
CO2
Server:
192.168.20.1
Critical Level:
15000ppm
Gateway:
192.168.20.1
Channel Name/State
General Settings
Relay Settings
CHANNEL 1
Units:
Metric
Relay 1
– 16:
Any Critical
thru to
Sample Interval:
30 Minutes
CHANNEL 16
Summary of Contents for Parasense GRM2 CO2 Series
Page 7: ...1 2 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 GENERAL ARRANGEMENT...
Page 14: ...2 7 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 NETWORK MODULE CONNECTIONS...
Page 74: ......
Page 75: ......
Page 76: ...2 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 GRM2 CO2 CONNECTION SCHEMATICS PS0748...
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ......
Page 81: ......
Page 82: ...3 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 ADC 104 GENERAL ARRANGEMENT PM2098...
Page 83: ......
Page 84: ...4 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 ADC 104 PANEL MOUNTING DETAILS PM2247...
Page 85: ......
Page 86: ...5 Operation Maintenance Manual Doc Ref MNGRM2CO2 REV 3 ADC 104 CONNECTION SCHEMATIC PS0753...
Page 87: ......
Page 88: ......
Page 89: ......
Page 91: ......
Page 93: ......
Page 95: ......
Page 96: ......