B.3.7. System Data Register 0x0010 (16 Dec) (R/W, 54 Bytes)
Variable
Type
Length
Description
Type
UI
2 bytes
Indicates EEPROM has been initialized if value = 300 DO NOT MODIFY
REV
Float
4 bytes
Firmware Rev Level DO NOT MODIFY
UNUSED
UI
2 bytes
Firmware Serial Number DO NOT MODIFY
Node
UC
1 byte
Network Slave Node # (valid values are 1-15). The default is that
indicated by the Node DIP Switch on main board.
Location
C
13 bytes
Array defining text name of unit
Stop_Bits
C
1 byte
Number of stop bits used in the MZ data stream. Default = 1. Other
available value is 2
Aud_Alarm
UC
1 byte
Sounds internal board buzzer on condition; 0 = no buzzer; 1= Alarm;
2=Fault; 3=Leak; 4=Spill; 5=Evacuate; 6=Monitor Off line (DEFAULT =
0)
Alarm_Ack_
Mode
UC
1 byte
Defines Alarm Operation. Manual Acknowledge = 0; Auto Acknowledge
= 1 (DEFAULT = 0)
Num_Zones
UC
1 byte
Number of install zones (Value initialized during auto detect during
Power On Self Test).
UNUSED
TIM
13 bytes
UNUSED
Rezero_Mode
UC
1 byte
Defines re-zero mode. Auto Re-zero = 0; Re-zero every zone = 1
(DEFAULT = 0)
Hold_Time
UI
2 byte
Length of zone hold interval in minutes (DEFAULT = 15 minutes)
UNUSED
UC
1 byte
Minimum detection limit (in PPM). Concentrations less than or equal this
value will read as 0 PPM (DEFAULT = 0 PPM)
Avg_Size
UC
1 byte
Size of running average used in computing PPM value. DO NOT
MODIFY.
Loop2_factor
Float
4 bytes
Defines PPM current loop output. (DEFAULT = 0.16 mA/PPM)
Serv_Mode_TO
UI
2 bytes
Service Mode Timeout value (in minutes). (DEFAULT = 60 MINUTES)
RS485_BAUD
UI
2 bytes
BAUD RATE for RS-485 connection (between RD and MZ monitor or
MODBUS master and MZ depending on the Network topology).
Default=9 (19.2K); other values are 8=9600, 7=4800
Mode
UI
2 bytes
UNUSED
B.3.8. Status Regi ster 0x011 (17 Dec) (R/W, 10 Byte s)
Variable
Type
Length
Description
Mode
UC
1 byte
Defines Operating Mode of MZ. 0 = normal Mode; 1 = Zone_Hold Mode; 2
= Diagnostic Mode; 3 = Service mode.
DO NOT MODIFY (use zone hold
register or service mode register to change this parameter)
State
UC
1 byte
Defines MZ Current State. 0 = Idle; 1 = Sampling; 2 = Zeroing; 3 = Warm
Up, 4 = Pressure Check
DO NOT MODIFY
Measuring
UC
1 byte
Value = 1 if unit is acquiring detector signal for running avg.
DO NOT
MODIFY
Acti ve_Zone
UC
1 byte
Current Zone being checked. 0=zone 1, 1=zone 2, etc.
Ma x _ Alarm
UC
1 byte
Indicates highest non-acknowledged alarm level
DO NOT MODIFY
Alarm_Count
UC
1 byte
Number of alarms that are currently active.
DO NOT MODIFY
UNUSED
UC
1 byte
UNUSED
Loop_Card
UC
1 byte
Value = 1 if 4-20 mA card has been detected.
DO NOT MODIFY
Fault
UI
2 bytes
Fault Flag Structure uses bitwise access to 16 bit word as defined in the
table below.
Summary of Contents for MultiZone
Page 52: ...Multi Zone Gas Monitors 46 P N 3015 5074 Rev 11 ...
Page 58: ...Multi Zone Gas Monitors 52 P N 3015 5074 Rev 11 ...
Page 60: ...Multi Zone Gas Monitors 54 P N 3015 5074 Rev 11 ...
Page 71: ...Multi Zone Gas Monitors P N 3015 5074 Rev 11 65 APPENDIX C SYSTEM MENU MAP ...
Page 72: ...Multi Zone Gas Monitors 66 P N 3015 5074 Rev 11 ...
Page 73: ...Multi Zone Gas Monitors P N 3015 5074 Rev 11 67 APPENDIX D AGENCY APPROVALS ...
Page 74: ...Multi Zone Gas Monitors 68 P N 3015 5074 Rev 11 ...
Page 76: ...Multi Zone Gas Monitors 70 P N 3015 5074 Rev 11 ...
Page 78: ...Multi Zone Gas Monitors 72 P N 3015 5074 Rev 11 ...