2.5. Connecting Communications Devices
2.5.1. Remote Display Module (RD) Connection
The MZ is connected to the optional RD using a shielded twisted pair instrument cable. The maximum
distance between the farthest MZ and RD is 4500 feet.
Use any of the remaining service knockouts to gain access to the interior of the monitor. The RS-485
communications wiring between the MZ and RD must be connected in the following manner:
1. Locate the RS-485 connector in the MZ (
see
Figure 2-3
on page 13
).
2. Connect one lead of a twisted shielded pair to the “B” connection point. Note the wire color.
3. Connect the second wire to the “A” connection point. Note the wire color.
4. Connect the ground to the “GND” connection point.
5. Locate the RS-485 connector marked “TO MONITORS” in the RD (
see this topic in the
RD manual).
This connector is located on the bottom of the RD PC board, second from the right.
6. Run the wire to the RD and connect the twisted shielded pair to the RS-485 “TO MONITORS”
connector using the same color code as used on the MZ.
2.5.2. Integrating with Building Management System s
The MZ may be connected directly to a Building Management System using a shielded twisted pair cable.
The cable from the Building Management System is connected to the RS-485 connector inside the MZ
monitor. MODBUS RTU is the standard communications protocol.
Use any of the remaining service knockouts to gain access to the interior of the monitor. Locate the RS-485
connector and remove it from the circuit board. Secure the wire leads to the connector orienting them as
shown in the diagram below. Check to make sure that the polarity matches the wiring to the Building
Management System. When you are through securing the connections, carefully plug the connector back
onto the circuit board.
2.5.3. Larger Integrated Systems
You may also connect the MZ monitor to a Building Management System through a Remote Display. In this
case, first connect the MZ to the RD as described above. Then, follow the instructions in the
Communications Connections
section of the RD manual for information on how to connect the RD to a
Building Management System.
Figure 2-6. RS-485 Connector
Summary of Contents for MultiZone
Page 52: ...Multi Zone Gas Monitors 46 P N 3015 5074 Rev 11 ...
Page 58: ...Multi Zone Gas Monitors 52 P N 3015 5074 Rev 11 ...
Page 60: ...Multi Zone Gas Monitors 54 P N 3015 5074 Rev 11 ...
Page 71: ...Multi Zone Gas Monitors P N 3015 5074 Rev 11 65 APPENDIX C SYSTEM MENU MAP ...
Page 72: ...Multi Zone Gas Monitors 66 P N 3015 5074 Rev 11 ...
Page 73: ...Multi Zone Gas Monitors P N 3015 5074 Rev 11 67 APPENDIX D AGENCY APPROVALS ...
Page 74: ...Multi Zone Gas Monitors 68 P N 3015 5074 Rev 11 ...
Page 76: ...Multi Zone Gas Monitors 70 P N 3015 5074 Rev 11 ...
Page 78: ...Multi Zone Gas Monitors 72 P N 3015 5074 Rev 11 ...