61
61
Point
Description
Variable
ModBUS
Address
BACnet
ID
Datatype
Read /
Write
Comment
No of Cells
No_Cells
30901
1401
INT
Read
1..6
No of pumps Running
No_PumpsRnng
30906
1406
INT
Read
1..6
Fluid Temp
LWtrTemp.PVal
30121
1501
REAL
Read
°F/°C
Outside temp
OutTemp.PVal
30123
1502
REAL
Read
°F/°C
Conductivity Sensor
WtrCondSensor.PVal
30125
1503
REAL
Read
µΩ/cm
Average Fan Speed (dry)
ActlFanSpeed
30201
1504
REAL
Read
rpm (Nexus Mode, Water
Saver Mode)
Average Fan Speed (wet)
ActlFanSpeedWet
30205
1506
REAL
Read
rpm (Nexus Mode, Energy
Saver Mode, Water Saver
Mode)
Average Fan Power (dry)
FanCurrPwrDry
30203
1505
REAL
Read
Watts/hp (Nexus Mode,
Water Saver Mode)
Average Fan Power (wet)
FanCurrPwrWet
30207
1519
REAL
Read
Watts/hp (Nexus Mode,
Energy Saver Mode, Water
Saver Mode)
Fan Speed 1..12
ActlFanSpeedInfo[1..12]
30911..30934
1507..1518
REAL
Read
rpm (2 Registers each)
Fan Power 1..12
EBMpapstFan_x_Mng.
BMSCurrentPower
30951..30974
1521..1532
REAL
Read
Watts/hp (2 Registers Each)
Fan Status 1..12
EbmpabstFan_x_Mng.
Online_EBM_1
10201..10212
1201..1212
BOOL
Read
Online / Offline
Common Alarm Fan 1..12
Al_CommonAlm_Fanx.
Active
10301..10312
1221..1232
BOOL
Read
Normal / Fault
Remote Input
Remote.PV
10221
1213
BOOL
Read
On / Off
Modules Operating (wet)
UnitLogic.No_EvapCell
30903
1403
UINT
Read
Number of modules operat-
ing wet
Modules Operating (dry)
UnitLogic.No_DryCell
30904
1404
UINT
Read
Number of modules operat-
ing dry
Operation Mode
BMSModeSw
40906
1701
UINT
Read /
Write
Nexus Mode /Energy Saver
Mode / Water Saver Mode
Conductivity Setpoint
UnitLogic.BMSWtrCond-
StPt
40907
1602
REAL
Read /
Write
µΩ/cm (default per BAC
water quality guidelines)
Table 15.
BMS Points Table
Appendix: iPilot
®
Control System
Software Menus
Alarm Logs (Record)