![background image](http://html1.mh-extra.com/html/bac/nexus-nxf-0403n-cs2ts-h1/nexus-nxf-0403n-cs2ts-h1_operation-and-maintenance-manual_3315538060.webp)
58
Screen
Ref.
Screen
Description
V07
Exporting system Alarm/Warning
• File Destination: Specify destination
• File name: Al_EXPORT_00
• Confirm: YES/NO
V08
Exporting system Data Log history
•
File Destination:
Specify destination
•
File Reference
: 00
•
Confirm:
YES/NO
V09
The entire system can be taken offline by
enabling manual mode from this screen.
In live or Manual Mode, follow system/
component(s) safety protocols..
V10
To test fan(s) in Manual Mode:
• Switch system to Manual Mode from screen
V09
• Select Fan
• On the next screen specify fan operating
speed
• Click Esc to come out of the screen
• Once the testing is done switch of the Fan by
entering “0” speed
In live or Manual Mode, follow system/
component(s) safety protocols..
V11
This screen is set in the factory and locked.
V12
This screen is set in the factory and locked.
V13
This screen is set in the factory and locked.
NOTE FOR V07 AND V08:
For
exporting the file to USB, switch off
the main disconnect on the control
panel and the main door, and insert
the USB into the controller. Close
and lock the panel main door, turn
ON the main disconnect and export
the file. Follow same procedure to
remove the USB from the controller.
NOTE (for V09 and V10):
To operate
system in live mode, ensure that all
manual operation is disabled and
OSV status on all the components
on all other screens is “NO”.
Table 11.
Point Overview Menu (V) (Continued)