18
• If not stored indoors in a controlled environment, some form of heating must be
utilized to prevent condensation from accumulating in the motor. This heating should
maintain temperature at a minimum of 9ºF (5ºC) above the ambient temperature of
the room, keeping it from dropping below the dew point where condensation could
form inside the motor.
• Rotate the motor shaft monthly to redistribute bearing grease.
Start-Up Preparation After Prolonged Storage
Keep in mind that start-up procedures after long periods of storage are just as important as
pre-shutdown procedures.
• Fans and motors should be thoroughly inspected and cleaned to restore them to pre-
storage condition.
• Reinstall all components, panels, and drain plugs (as applicable), and remove all
protective coverings.
• For units stored prior to installation, conduct rigging procedures as directed
in the unit’s
Rigging and Assembly Instructions
, by contacting your local BAC
Representative.
• Perform an insulation test to ensure satisfactory insulation resistance.
• Conduct full start-up procedure as stated in “Start-Up” on
page 8
. Be especially
thorough for cleaning and inspection prior to start-up.
DANGER:
Rotating equipment
will cause severe personal injury
or death to persons who come in
contact. Do not perform any service,
maintenance, or inspection on or
near the fan(s), motor(s), or inside
the unit without first ensuring
that the fans and pump motors
are disconnected, locked out, and
tagged out.