Point Overview Menu (V)
The screens in Point Overview are developed to troubleshoot and test different components
in Manual Mode.
Screen
Ref.
Screen
Description
V01
Shows operating values (read only)
• Leaving Process Fluid Temp
• Ambient Temperature
• Water Conductivity
V02
Screen shows Pump status based on unit configu-
ration
•
Example
– Unit configured for 4 modules and
all pumps are normal
V03
Screen shows the basin water level switch status
and remote dry contact status (read only)
•
“WaterLvlHigh”:
High Level Switch
•
“WaterLvlLow”:
Low Level Switch
• “
Remote Ov/Off”:
Remote dry contact
V04
Pump status and testing in manual mode (Read/
Write)
•
OSV:
Out of status value (manual mode), for
testing pump and pump wiring turn ON the OSV
status on the Pump.
•
CMD:
Command, when the system is live (not in
manual mode) this should show “ON”
V05
Drain and make-up testing in manual mode
(Read/Write)
•
OSV - Out of status value (manual mode):
To test heater and corresponding wiring, turn
ON the OSV status on the Heater. Ensure that
heater control panel is turned ON.
•
CMD - Command, when the system is live (not
in manual mode)
: This will show the current
state of the component
V06
Heater and heater wiring testing in Manual Mode
(Read/Write). The screen will be only available if
the Heater option is purchased on the product
•
OSV:
Out of status value (manual mode), for
testing Heater and corresponding wiring turn
ON the OSV status on the Heater. Also make
sure the Heater control panel is turned ON as
well
•
CMD:
Command, when the system is live (not
in manual mode) this should show the current
state of the component.
NOTE:
For V04 - V06, to run system
in live mode, ensure that all pump
OSV statuses are “NO”.
Table 11.
Point Overview Menu (V)
Appendix: iPilot
®
Control System
Software Menus
User Menu (E)
Point Overview Menu (V)