The water diverter can be accessed by opening the panel located behind the spray water
basin. Quarterly, inspect and remove any trash or debris that may have accumulated
from the water diverter and flush with fresh water using a standard garden hose. This will
remove the sediment, which can collect during operation.
Figure 24.
Spray Branch Removal
Water Distribution System
Spray Branches and Nozzles
Water is distributed through a corrosion resistant polyvinyl chloride (PVC) water
distribution system (optional steel distribution is available). Inspect the spray branches
and nozzles quarterly. To inspect the water distribution system:
• Operate the equipment in Manual Mode, and turn the spray pump On, fan(s) Off.
• Remove the spray access panel.
• Check to see that the spray is uniform. Clean any clogged nozzles, and if additional
cleaning is necessary. The distribution header can be removed for cleaning by
loosening the rubber sleeve on the spray branch.
• Verify that there are no leaks in the water distribution system.