66
User Manual v2.0
MAG
MENU
I / O
» Active output freq.
Select to disable the pulse output (which becomes PWM, pulse width modulation)
and frequency enable output.
• PROGRAMMABLE OUTPUT
It is possible to choose among the following options for the programmable
output:
- Enabled/disabled
- Reverse Flow
- Max flow threshold
- Min flow threshold
- MAX/MIN flow threshold
- Dosing
- Excitation failure
- Empty Pipe
- All alarms
• PROGRAMMABLE INPUT
It is possible to choose among the following options for the programmable
input:
- Enabled/disabled
- Resetting p+
- Resetting p-
- Resetting p+/p
- P resetting and block
If the programmable output is set to “dosing,” the programmable input will
be the same and automatically used in the option dosing and it cannot
be changed.
• DOSAGE
Set the volume to be dosed. Available only with powered version.
In order to guarantee adequate precision, the dosing duration must be
greater than 60 seconds with full speed flow.
• PROGRAMMABLE OUTPUT LOGIC
It is possible to change the logic of the programmable output by choosing
between NO/NC – normally open, normally closed.
In battery mode the output is always NO.
Alimentazione
+
-
24 VDC
24 VDC
Pompa a
valvola
RELE
max. 50mA
Fig. 92 | Example of Connection for the Programmable Output
Power supply
Pump or
Valve