AB-6387
3
CAUTION
Installation and wiring of the actuator must
be performed by personnel qualified to do
instrumentation and electrical work.
Mistakes in installation or wiring may cause
fire or electric shock.
All wiring must comply with applicable codes
and ordinances.
Otherwise there is a danger of fire.
Use crimp terminals with insulation for
connections to the product terminals.
Failure to do so may cause a short circuit
leading to fire or device failure.
CAUTION
Tighten the terminal screws with the specified
torque.
Insufficient tightening of the terminal screws
may cause fire or overheating.
Do not touch any parts unless instructed to
do so in this manual.
Failure to observe these precautions may
result in burns, because actuator parts reach
a high temperature.
Model Numbers
Model number
Specification
Power supply
Control signal
Angular
stroke
Operating time for one
stroke
Output
torque
Remarks
50 Hz
60 Hz
MY3000F0200
24 V AC
Nominal 135 Ω
feedback potentiometer
160°
69 s
58 s
12.5 N·m
—
MY3000F0400
35 s
29 s
6 N·m
High speed
motor type
MY3000E0200
Nominal 135 Ω
resistance Input
69 s
58 s
12.5 N·m
—
MY3000G0200
4–20 mA DC
—
MY3000G9200
85–264 V AC
72 s
72 s
—
MY3000V0200
24 V AC
2–10 V DC
69 s
58 s
—
MY3000D0200
SPDT floating
ON/OFF
operation
Note: The auxiliary switch unit is an optional part.
z
Options
Item
Model number
Specification
Valve linkage
Q455
Damper linkage
Q605
Power transformer
AT72-J1
Primary voltage
100 V AC, 200 V AC, or 220 V AC
Secondary
voltage
23 V AC
Power frequency 50–60 Hz
Waterproof connector*1 83104346-
003
Applicable wire
Dia. 7–9 mm
Auxiliary switch unit
83174065-
102
Number of
auxiliary
switches
4
Max. applied
voltage, current
30 V DC, 100 mA*
2
(inductive load includes inrush
current.)
250 V AC, 100 mA*
2
(inductive load includes inrush
current.)
Operation range SW1 to SW4:
Variable from 5 % (fully closed) to 95 % (fully open)
Can be changed by setting the dials A to D.
*
1 Required to maintain IP54.
*
2 If the applied current exceeds 100 mA, please contact Azbil Corporation.