background image

AB-6387

2

Safety Precautions

Please read instructions carefully and use the product 

as specified in this manual. Be sure to keep this 

manual nearby for quick reference.

Restrictions on Use

This product was developed, designed, and 

manufactured for general air conditioning use.
Do not use the product in a situation where human 

life may be at risk or for nuclear applications in 

radiation controlled areas. If you wish to use the 

product in a radiation controlled area, please 

contact Azbil Corporation.
Particularly when the product is used in the 

following applications where safety is required, 

implementation of fail-safe design, redundant 

design, regular maintenance, etc., should be 

considered in order to use the product safely and 

reliably. 
• Safety devices for protecting the human body
•  Start/stop control devices for transportation 

machines

• Aeronautical/aerospace machines
For system design, application design, instructions 

for use, or product applications, please contact 

Azbil Corporation.
Azbil Corporation bears no responsibility for 

any result, or lack of result, deriving from the 

customer's use of the product.

Recommended Design Life

It is recommended that this product be used within 

the recommended design life.
The recommended design life is the period during 

which you can use the product safely and reliably 

based on the design specifications. 

If the product is used beyond this period, its 

failure ratio may increase due to time-related 

deterioration of parts, etc. 
The recommended design life during which the 

product can operate reliably with the lowest failure 

ratio and least deterioration over time is estimated 

scientifically based on acceleration tests, 

endurance tests, etc., taking into consideration the 

operating environment, conditions, and frequency 

of use as basic parameters. 
The recommended design life of this product is 10 

years.
The recommended design life assumes that 

maintenance, such as replacement of the limited 

life parts, is carried out properly. 

Refer  to  the  section  on  maintenance  in  this 

manual.

Warnings and Cautions

WARNING

Alerts users that improper handling 

may cause death or serious injury.

CAUTION

Alerts users that improper handling 

may cause minor injury or material 

loss.

Signs

Notifies users that specific actions are 

prohibited to prevent possible danger. 

The symbol inside 

 graphically indicates 

the prohibited action.  (For example, the 

sign on the left means that disassembly is 

prohibited.)

Instructs users to carry out a specific 

obligatory action to prevent possible danger. 

The symbol inside 

 graphically indicates the 

actual action to be carried out.  (For example, 

the sign on the left indicates general 

instructions.)

 

WARNING

Before wiring, setting, or maintenance, be 

sure to turn off the power to this product.

Failure to do so may result in electric shock 

or device failure.

Be sure to ground this product with a ground 

resistance of less than 100 Ω.

Improper grounding may cause electric 

shock or malfunction.

After wiring, setting, or maintenance, be sure 

to reattach the cover.

Failure to do so may result in electric shock.

Before setting or engineering work, be sure 

to turn off the power to the output terminals. 

Failure to do so may cause electric shock.

 

CAUTION

Provide a circuit protector  (e.g., a fuse or 

circuit breaker) for the power source. 

Failure to do so may cause a short circuit 

leading to fire or device failure.

Install, wire, and use this product under the 

conditions specified by this manual. 

Failure to do so may cause fire or device 

failure.

Do not put a load or weight on this product. 

Doing so may damage the product.

Summary of Contents for MY3000 00 Series

Page 1: ...xerting proportional control when combined with the electric proportional controller such as Neostat Model TY900_Z insertion type temperature controller Model TY9800 4 20 mA DC input type exerting pro...

Page 2: ...sts etc taking into consideration the operating environment conditions and frequency of use as basic parameters The recommended design life of this product is 10 years The recommended design life assu...

Page 3: ...ue Remarks 50 Hz 60 Hz MY3000F0200 24 V AC Nominal 135 feedback potentiometer 160 69 s 58 s 12 5 N m MY3000F0400 35 s 29 s 6 N m High speed motor type MY3000E0200 Nominal 135 resistance Input 69 s 58...

Page 4: ...eedback potentiometer F B potentiometer total resistance nominal 135 Max applied voltage 5 V DC Nominal 135 resistance Input 4 20 mA DC input Input impedance 125 2 10 V DC input Input impedance 1 M or...

Page 5: ...tdoor cover optional parts etc to avoid direct sunlight Mounting position Refer to Installation Mounting position Manual operation Available Refer to Installation Manual open close operation Insulatio...

Page 6: ...ixing the cover Three screws are provided in total Bracket Base for mounting the main body Mounting holes Holes in the bracket for mounting the actuator Mount the actuator with M6 screws Cover Plastic...

Page 7: ...Models Q455C or Q455D To attach the valve linkage refer to AB 4051 Valve Linkages Mod els Q455C Q455D Q455F Specifications Instructions z z When using with the damper When this product is used with t...

Page 8: ...y Switch Unit Optional WARNING Before beginning setup work be sure to turn off the power to this product Failure to do so may result in electric shock or device failure Before setting or engineering w...

Page 9: ...dials A B C D After setting the auxiliary switches check that they operate as intended The operation range of the auxiliary switches is as follows Setting range valve position from 5 to 95 Repeatabili...

Page 10: ...Y3000E0200 4 5 6 7 To controller 24 V AC power Open F G R B W T2 T1 1 3 2 Figure 13 z z 4 20 mA DC input Model MY3000G0200 Model MY3000G9200 4 5 6 4 20 mA DC inputs to controller 24 V AC power or 85 2...

Page 11: ...o the terminal W on either the motor side or the controller side Figure 18 Connection to Neostat z z 4 20 mA DC input Model MY3000G0200 Model MY3000G9200 Model R35TC0 Model R36TC0 Control motor 4 20 m...

Page 12: ...an abnormal condition such as disconnection in the actuator an abnormal input signal failure of the feed back potentiometer due to its product service life the minimum opening position cannot be maint...

Page 13: ...not internally connected 3 Do not implement a daisy chain wiring passing through this product s power terminals Figure 24 z z 2 10 V DC input Model MY3000V0200 Input signals and power are shared Model...

Page 14: ...s Damages on the product Operation status 6 months Check that the valve is smoothly opened or closed Check that no abnormal sound or vibration is observed Regular inspection Whenever necessary Check t...

Page 15: ...AB 6387 15 Disposal Dispose of this product as industrial waste in accordance with your local regulations Do not reuse all or any part of the product...

Page 16: ...n Infilex is a trademark of Azbil Corporation Specifications are subject to change without notice http www azbil com 1 12 2 Kawana Fujisawa Kanagawa 251 8522 JAPAN Building Systems Company 16 AB 6387...

Reviews: