Maintenance

 

WARNING

Before doing maintenance, be sure to turn off the power to this product.

Failure to do so may result in electric shock or device failure.

After maintenance, be sure to reattach the terminal cover.

Failure to do so may result in electric shock.

 

CAUTION

Do not put a load or weight on this product.

Doing so may damage the product.

Do not touch any parts unless instructed to do so in this manual.

Failure to observe these precautions may result in burns, because actuator parts reach a high 

temperature.

 

If the product is not operated for a long period, execute valve open and close operations once a month or so.

 

Execute maintenance according to Table 1.

 

Once every six months or so, visually check that the product operates smoothly.  

 

if a trouble occurs as described in Table 2, take appropriate measures according to the symptom. Although the 
measures are taken, if the trouble cannot be recovered, please contact Azbil Corporation.

Table 1  Inspection items and inspection method

Item

Inspection 

cycle

Inspection method

Visual check

6 months

 Loose bolts

 Damages on the product.

Operation status

6 months

 Check that the valve is smoothly opened or closed.

 Check that no abnormal sound or vibration is observed.

Regular inspection

Whenever 
necessary

 Check that the valve is smoothly opened or closed.

 Check that no abnormal sound or vibration is observed.

 Check that there is no hunting observed with.

Table 2  Troubleshooting

Abnormal phenomenon

Where to inspect

Measure

The valve is not smoothly opened or 
closed.
The valve stops halfway.
The valve does not operate.

Check that the power line and the input signal 
are correctly fed.
Loose terminals

Check that wires are firmly connected, no dis

-

connected wire.

Check the power supply voltage and the con-
troller.

Retighten the terminals.

Check the wirings.

The auxiliary switches do not operate.

Check the conditions of the auxiliary switch 
cam.
Loose terminals

Check that wires are firmly connected, no dis

-

connected wires are observed.

Do settings again.

Retighten the terminals.

Check the wirings.

The control sensitivity is deteriorating.
The torque is decreasing.

Check that wires are firmly connected, no dis

-

connected wires are observed.
Loose terminals
Check the supplied voltage.

Check the wirings.

Retighten the terminals.

Adjust the supplied voltage.  (Excluding the 
85–264 voltage type)

Summary of Contents for MY3000 00 Series

Page 1: ...xerting proportional control when combined with the electric proportional controller such as Neostat Model TY900_Z insertion type temperature controller Model TY9800 4 20 mA DC input type exerting pro...

Page 2: ...sts etc taking into consideration the operating environment conditions and frequency of use as basic parameters The recommended design life of this product is 10 years The recommended design life assu...

Page 3: ...ue Remarks 50 Hz 60 Hz MY3000F0200 24 V AC Nominal 135 feedback potentiometer 160 69 s 58 s 12 5 N m MY3000F0400 35 s 29 s 6 N m High speed motor type MY3000E0200 Nominal 135 resistance Input 69 s 58...

Page 4: ...eedback potentiometer F B potentiometer total resistance nominal 135 Max applied voltage 5 V DC Nominal 135 resistance Input 4 20 mA DC input Input impedance 125 2 10 V DC input Input impedance 1 M or...

Page 5: ...tdoor cover optional parts etc to avoid direct sunlight Mounting position Refer to Installation Mounting position Manual operation Available Refer to Installation Manual open close operation Insulatio...

Page 6: ...ixing the cover Three screws are provided in total Bracket Base for mounting the main body Mounting holes Holes in the bracket for mounting the actuator Mount the actuator with M6 screws Cover Plastic...

Page 7: ...Models Q455C or Q455D To attach the valve linkage refer to AB 4051 Valve Linkages Mod els Q455C Q455D Q455F Specifications Instructions z z When using with the damper When this product is used with t...

Page 8: ...y Switch Unit Optional WARNING Before beginning setup work be sure to turn off the power to this product Failure to do so may result in electric shock or device failure Before setting or engineering w...

Page 9: ...dials A B C D After setting the auxiliary switches check that they operate as intended The operation range of the auxiliary switches is as follows Setting range valve position from 5 to 95 Repeatabili...

Page 10: ...Y3000E0200 4 5 6 7 To controller 24 V AC power Open F G R B W T2 T1 1 3 2 Figure 13 z z 4 20 mA DC input Model MY3000G0200 Model MY3000G9200 4 5 6 4 20 mA DC inputs to controller 24 V AC power or 85 2...

Page 11: ...o the terminal W on either the motor side or the controller side Figure 18 Connection to Neostat z z 4 20 mA DC input Model MY3000G0200 Model MY3000G9200 Model R35TC0 Model R36TC0 Control motor 4 20 m...

Page 12: ...an abnormal condition such as disconnection in the actuator an abnormal input signal failure of the feed back potentiometer due to its product service life the minimum opening position cannot be maint...

Page 13: ...not internally connected 3 Do not implement a daisy chain wiring passing through this product s power terminals Figure 24 z z 2 10 V DC input Model MY3000V0200 Input signals and power are shared Model...

Page 14: ...s Damages on the product Operation status 6 months Check that the valve is smoothly opened or closed Check that no abnormal sound or vibration is observed Regular inspection Whenever necessary Check t...

Page 15: ...AB 6387 15 Disposal Dispose of this product as industrial waste in accordance with your local regulations Do not reuse all or any part of the product...

Page 16: ...n Infilex is a trademark of Azbil Corporation Specifications are subject to change without notice http www azbil com 1 12 2 Kawana Fujisawa Kanagawa 251 8522 JAPAN Building Systems Company 16 AB 6387...

Reviews: