20
32
Bulk charging time
(C.V stage)
Automatically (Default):
If selected, inverter will judge this
charging time automatically.
5 min
The setting range is from 5 min to
900 min. Increment of each click is
5 min.
900 min
If “USE” is selected in program 05, this program can be set up.
33
Battery equalization
Battery equalization
Battery equalization disable
(Default)
If “Flooded” or “User-Defined” is selected in program 05, this
program can be set up.
34
Battery equalization
voltage
Default setting is 58.4V.
Setting range is from 48V ~ 64V.
Increment of each click is 0.1V.
35
Battery equalized time
60min (Default)
Setting range is from 5min to
900min. Increment of each click is
5min.
36
Battery equalized timeout
120min (Default)
Setting range is from 5min to 900
min. Increment of each click is 5
min.