Page 10
AXIS Q6032-C/Q6034-C/Q6035-C Installation Guide
Network connector SFP (external) -
Two SFP connectors (100Base-FX/1000Base-X) for network
connectivity.
Each RJ-45 and SFP connector has its own dip switch. The dip switches control how the port
forwards data. See the User Manual for more information.
Network connector (internal) -
Two 2-pin Ethernet terminal blocks.
I/O connector (external) -
6-pin configurable I/O terminal block, which
is connected to the camera through the multi-connector cable. Use with
external devices in combination with, for example, tampering alarms,
motion detection, event triggering, time lapse recording and alarm
notifications. In addition to ground and power (DC output), the I/O terminal connector provides the
interface to:
• Digital output — For connecting external devices such as relays and LEDs. Connected
devices can be activated by the VAPIX® Application Programming Interface, output buttons
on the Live View page or by an Action Rule. The output will show as active (shown under
System Options > Port & Devices > Port Status
) if the alarm device is activated.
• Digital input — An alarm input for connecting devices that can toggle between an open and
closed circuit, for example: PIRs, door/window contacts, glass break detectors, etc. When a
signal is received the state changes and the input becomes active (shown under
System
Options > Port & Devices > Port Status
).
I/O connector (internal) -
2-pin I/O terminal block.
Dip switch position
Description of use
Default (middle)
B
When connecting to the network, directly or through a router or network
switch.
Left
A
When connecting to a camera or a device that is not intended for viewing
data.
Right
C
When connecting to another media converter switch.
Function
Pin
Notes
Specifications
GND
1, 4, 6 Ground
DC output
2
Power out
12 V DC, 50 mA
Configurable
(Input or
Output)
3,5
Digital input
0 to +30 V DC
Digital output (transistor – open collector)
Max load = 100 mA
Max voltage = +30 V DC
3
6
5