7
Operation
Setting the switching point
Switching points are set via the teach button
(2)
(see
).
1.
Apply the vacuum/pressure for the desired teach point.
2.
Press button
(2)
for approx. 2 s to set the teach point. Both LEDs will flash.
–
Vacuum switch:
Switch-on point (SP) = teach point (TP) -20% of TP
(Example: TP = -700 bar, SP = -560 mbar)
Fixed hysteresis (2% F.S. = 20 mbar)
–
Pressure switch:
Switch-on point (SP) = teach point (TP) -20% of TP
(Example: TP = 6 bar, SP = 5.7 bar)
Fixed hysteresis (2% F.S. = 200 mbar)
Resetting to factory settings
1.
Disconnect the PE 6 from the operating voltage.
2.
Hold down the
(2)
button and apply the operating voltage.
Both LEDs will flash.
3.
Press button
(2)
for approx. 2 s until both LEDs go out.
Factory setting
8
Maintenance
The PE 6 is maintenance-free. Please contact the service department at AVENTICS if
you have any technical problems.
9
Cleaning and servicing
How to clean the PE 6:
1.
Make sure that all relevant system parts are not under voltage or pressure.
2.
Clean the PE 6.
10 Disposal
O
Dispose of the PE 6 in accordance with the applicable national regulations.
CAUTION
Too high pressure
A too high pressure can damage the PE 6:
W
The PE 6 vacuum switch has only been designed for operation with vacuums
(referring to atmosphere). Pressures up to 5 bar do not cause damage to the
switch; however, pressures from 2 bar may adversely affect precision and
service life.
W
The PE 6 pressure switch is designed for a maximum overpressure of 15 bar.
O
Note the maximum permissible pressure values. This information can also be
found on the rating plate and in the technical data.
When switching inductive loads, use a recovery diode on the load!
Variants
Switching point
Vacuum switch
-600 mbar
Pressure switch
6 bar
CAUTION
Solvents and aggressive cleaning agents
Solvents and aggressive cleaning agents could damage the PE 6.
O
Only use water for cleaning and, if necessary, kerosene or benzine.
4
1
11 Technical data
PE 6
Vacuum switch
(MNR R412007804)
Pressure switch
(MNR R412007805)
Sensor type
Piezo-resistive
Measuring medium
Non-aggressive gases, dry air
Medium
Compressed air in accordance with ISO 8573-1:2010
(max. particle size: 40 μm; pressure dew point: ≤ 3 °C;
oil content: max. 1 mg/m3)
Pressure range
-1 to 0 bar
0 to 10 bar
Operating voltage
10 to 30 VDC, protective extra-low voltage (PELV in
accordance with IEC 364-4-41), residual ripple (P-P)
max. 10%
Switch output
1x PNP, NO ("make" contact), max. 200 mA
1)
1) When switching inductive loads, use a recovery diode on the load.
Switching state display
Via 2 yellow LEDs
Hysteresis
2% F.S.
Switching point: 20 mbar
Switching point: 200 mbar
Protective circuit
Operating voltage protected against polarity reversal,
switch output is short circuit-proof, timed
Repetitive precision
±1% of full scale
Temperature influence
±3% of full scale in the operating temperature range
Electrical connection
Push-in fitting, M8x1, 3-pin
2)
2) Max. cable length: 30 m
Measuring medium
connection
Push-in fitting
Protection class
IP40 (according to EN 60529/IEC 529)
Insulating resistance
>100 MW at 500 VDC
Testing voltage
1000 VDC, 1 min
Interference emission
Tested in accordance with EN 61000-6-3:2007
Interference immunity
Tested in accordance with EN 61000-6-2:2005
Switching times
< 2 ms
Current consumption
< 20 mA
Temperature ranges
Operation: 0 to +60°C, medium: 0 to +50°C, storage: -25
to +80°C
Permissible humidity
10 to 90% rel. humidity without condensation or ice
formation
Resistance to
overpressure
5 bar
15 bar
3)
3) 100,000 cycles < 1 s
Dimensions
See
Weight
Approx. 6 g
5
AVENTICS
| PE6 | R412008995–BDL–001–AC | English
4