Table 13. Electrical Input
Model
Default Input
(Voltage/Current)
Selectable Input
Voltages
Voltage Range
at 100% Load
1000 VA, 120V
120V / 8.3A
100*, 110**, 120, 127
80–138 Vac
1500 VA, 120V
120V / 12.5A
100*, 110**, 120, 127
80–138 Vac
3000 VA, 120V
120V / 25A
100*, 110**, 120, 127
90–138 Vac
1000 VA, 208/230/240V
230V / 4.3A
200*, 208**, 220, 230, 240
160–276 Vac
1500 VA, 208/230/240V
230V / 6.5A
200*, 208**, 220, 230, 240
160–276 Vac
3000 VA, 208/230/240V
230V / 13.0A
200*, 208**, 220, 230, 240
180–276 Vac
* 100V and 200V are derated by 20%.
** 110V and 208V are derated by 10%.
Table 14. Electrical Input Connections
Model
Input Connection
Input Cable
1000 VA, 120V
5-15P
Attached line cord
1500 VA, 120V
5-15P
Attached line cord
3000 VA, 120V
L5-30P
Attached line cord
1000 VA, 208/230/240V
IEC C14-10A
Schuko 10A to IEC 320-10A
1500 VA, 208/230/240V
IEC C14-10A
Schuko 10A to IEC 320-10A
3000 VA, 208/230/240V
IEC C20-16A
Schuko 16A to IEC 320-16A