OPERATION
Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual
S
164201765 Rev 1
42
Starting the UPS on Battery
NOTE
Before using this feature, the UPS must have been powered by utility power with
output enabled at least once.
NOTE
Battery start can be disabled. See the “Start on Battery” setting in “User Settings”
on page 36.
To start the UPS on battery:
1.
Press the
button on the UPS front panel until the UPS front panel
display illuminates and shows a status of “UPS starting . . .”
The UPS cycles through Standby mode to Battery mode. The
indicator illuminates solid. The UPS supplies power to your
equipment.
2.
Check the UPS front panel display for active alarms or notices
besides the “UPS on Battery” notice and notices that indicate
missing utility power. Resolve any active alarms before continuing.
See “Troubleshooting” on page 79.
Check the UPS status from the front panel to view the active
alarms. Correct the alarms and restart if necessary.
3.
Press the
ESC
button until the start screen appears.
UPS Shutdown
To shut down the UPS:
1.
Press the
button on the front panel for three seconds.
The UPS starts to beep and shows a status of “UPS off
pending . . .” The UPS then transfers to Standby mode, and the
indicator turns off.
NOTE
Releasing the
button before three seconds returns the UPS to its original
operating mode.
2.
Switch off utility power where the UPS is connected.