OPERATION
Avaya 9130 1000–3000 VA UPS Site Preparation, Installation and Operator’s Manual
S
164201765 Rev 1
45
Configuring Load Segments
Load segments are sets of receptacles that can be controlled by power
management software or through the display, providing an orderly
shutdown and startup of your equipment. For example, during a power
outage, you can keep key pieces of equipment running while you turn
off other equipment. This feature allows you to save battery power.
Each UPS has two configurable load segments:
S
Load Segment 1: Upper outlets and higher rated outlets if available.
S
Load Segment 2: Lower outlets
See “Rear Panels” on page 76 for load segments for each UPS model.
To control the load segments with power management software, see
your power management software manual for details (refer to the
Software Suite CD or www.powerware.com/avaya for the latest
information).
To control the load segments through the display:
1.
Press any button to activate the menu options, then select
CONTROL and LOAD SEGMENTS.
2.
Set the desired load segment ON or OFF, and ENTER to confirm.
3.
Set the other load segment if applicable.
To set the restart and shutdown delay times for each load segment:
1.
Press any button to activate the menu options, then select
SETTINGS, USER SETTINGS and AUTOMATIC START DELAY.
2.
Set the restart delay for one load segment, and ENTER to confirm.
3.
Set the other load segment if applicable.
4.
Select AUTOMATIC ON BATTERY SHUTDOWN.
5.
Set the shutdown delay for one load segment, and ENTER to
confirm.
6.
Set the other load segment if applicable.
NOTE
Load segment On/Off commands issued through the Control menu overrule the user
settings for load segments.