AUX Air Conditioner Service manual
5
ASW-H09A+09A4/EA(L)2R1-I
Model No
Items
Indoor Unit A
(System A)
Indoor Unit B
(System B)
Outdoor Unit
Type
Wall mounted model Heating pump
Cooling kw
2.5
2.5
/
Dehumidify kg/h 1.0 1.0 /
Heating kw
2.75
2.75
/
Noise level
dB(A)
38
38
62
Cooling 2.6
2.6
/
Performance
EER
Heating
W/W
2.6 2.6 /
Power supply
φ
-V-Hz
1 / 220-240V~/ 50Hz
Cooling 960
960
1820
Rated input
Heating
W
950 950 1780
Cooling 4.17
4.17
7.91
Rated current
Heating
A
4.13 4.13 7.74
Length m
2
2
4.8
Supply cord
Class
/
250V 10A
250V 10A
400V 25A
Starting Current
A
21.7
21.7
/
Electrical Data
Fuse capacity
A 3.15
3.15 3.15
Refrigerant/Charge g
R410a/750 R410a/800 /
Type /
Rotary
Rotary
/
Model /
PA108X1C-4FZDE PA108X1C-4FZDE
/
Rated input W
885/915
885/915
/
Compressor
Overload
Protector
/ B160-135-241E
MRA13430-9087
B160-135-241E
MRA13430-9087
/
Heat exchanger
Row*Hole
2*11
2*11
1*31
Type Capillary
tube
Refrigerating System
Expansion device
Specification(mm)
φ
2.6*500+
φ
2.6*800
φ
2.6*700+
φ
2.6*700
/
Air Volume
m3/h
420
420
/
Cooling r/min
980/900/850/800
980/900/850/800
860
Fan Speed
H/M/L/Q
Heating r/min
980/900/850/850
980/900/850/850
860
Fan type
/
Cross flow
Cross flow
Propeller fan
Fan System
Fan motor output
W
13
13
6
8
Connecting
Pipe
Gas /Liquid OD(mm)*L(mm)
Φ
9.52×5000/
Φ
6.35×5000
Connection
Drainage Pipe
OD(mm)*L(mm)
Φ
14×780
Suitable area
m2
12-17
12-17
/
Net dimensions
(W x H x D)
mm 745*250*210
745*250*210
331*846*901
Others
Net weight
kg
9.5
9.5
65
Summary of Contents for EA Series
Page 1: ...AUX One to Two Split Air Conditioner Service Manual EA EL HS Series ...
Page 48: ...AUX Air Conditioner Service manual 46 9 Fault analysis of major parts ...
Page 58: ...AUX Air Conditioner Service manual 56 b Single Cooling Model ...
Page 60: ...AUX Air Conditioner Service manual 57 Section 10 Service Record Date Page Part Cause Report ...