AUX Air Conditioner Service manual
38
2. No power supply
(
out of work completely
)
-tentative diagnosis
2.1. Check item
1) Does the input voltage is correct
?
2) Does AC power wires connected correctly
?
3) Does the output voltage of voltage stabilizer l7805 (ic2) is correct
?
4) Does between indoor and outdoor unit communication is normal
?
2.2. Fault diagnosis procedure
Note
:
There is according with an outdoor unit and two indoor unit.and a set of PCB. Please check them
accordingly.
1 Unplug the indoors and outdoors and re-plug after about 5 seconds
2 Listen if noise from buzzer or not?
3 Check the indoor power wire connection and the fuse are intact or not?
4 The outdoor PC board switched on communication signal or not?
5 Check the indoor/outdoor communication connection normal.or not?
6 Check the primary voltage of transformor
7 Check the transformor is normal or not?