4
、
output frequencies: F = Fo +
Δ
F
Δ
F =Kp×
(
En+1- En
)
+ Ki×En+1 + Kd×
(
En+1 - 2En + En-1
)
Fo=20
,
Kp=6.0, Ki=8.0, Kd=2.0 (EEEPROM can adjust)
a .Frequency range: 20Hz
~
85Hz,if F
<
20Hz
,
20Hz is the bottom
;
if F
>
85Hz
,
85 Hz is the
top.
b. En+1=Tr-Ts
,
En+1 range: -3
~
+13
c. If consecutive time of En+1
≤
-2 is 2min,the compressor will be shut down.
d. Starting with power, if En+1
≤
0,the compressor won’t work, if En+1
>
0,the compressor will
open.
e. There are no temperature compensation for the firstly open, when the compressor start, it
will be Tr temperature compensation, for example, compensate with 2
℃
, the Tr=Tr
(
true
)
+2
℃
.
f. when the compressor shut down, the indoor fan will still running according to the setting
wind.
The above is the work frequency without any other restrictions on high-frequency and
protections on down-frequency; if there are restrictions and protections, the frequency vale
will adjust on the above value, and the adjust value according to the certain mode and the
fault protection instructions.
5
、
In cooling mode, it can set as automatic wind, high wind, medium wind, low wind to meet
requirement, and the automatic wind speed can controlled as follows
:
when Tr
≥
Ts+3
℃
,High wind
when Ts+1
℃
≤
Tr
<
Ts+3
℃
,Medium wind
when Tr
<
Ts+1
℃
,low wind
At automatic speed, when the wind speed from low switching high, the wind speed without
delay; while from high switching low, there will be delay with 3 min.
6
、
The functions of this model are as follows: time setting, sleep, auto start, Anion, high
efficiency
7
、
According to cooling operation, there are anti-freeze protection of indoor coil , temperature
thermal protection of outdoor exhaust, over-current protection, overheating protection of
compressor, fault protection of indoor fan , sensor fault protection, fault protection of module,
fault protection of communication, 3min delay protection of compressor.
8
、
First start with power without 3 min delay protection.
9
、
The order of on/off of Outdoor fan and compressor: The compressor will open 5s later after
outdoor fan open and the outdoor fan will shut down 15s later after the compressor shut down.
10
、
The restrictions and protection for Ta when cooling.
When Ta
≥
47
℃
,it open as cooling mode normal, the maximum work frequency of
23
Summary of Contents for ASW-H09A4/SAR1DI
Page 1: ...FOR Split Wall Mounted Series R410a DC Inverter ASW H09A4 SAR1DI ASW H12A4 SAR1DI 2008 ...
Page 6: ...Remote Controller Instructions 4 ...
Page 7: ...5 ...
Page 8: ...6 ...
Page 9: ...7 ...
Page 10: ...8 ...
Page 11: ...9 ...
Page 12: ...10 ...
Page 13: ...11 ...
Page 14: ...12 ...
Page 15: ...13 ...
Page 16: ...14 ...
Page 17: ...15 ...
Page 42: ...Exploded Pictures 1 Indoor unit exploded picture ASW H09A4 SAR1DI 40 ...
Page 44: ... 2 Outdoor unit exploded picture ASW H09A4 SAR1DI 42 ...
Page 46: ... 3 Indoor unit exploded picture ASW H12A4 SAR1DI 44 ...
Page 48: ... 2 Outdoor unit exploded picture ASW H12A4 SAR1DI 46 ...