(7)Expelling the air in the pipes and the indoor unit
Expelling the air: humid air in the refrigerating system might cause
trouble of compressor.
①
Take off the cover from the stop valve and T-branch valve.
②
Take off the auxiliary cover from the T-branch valve.
③
Turn the stop valve rod anti-clock wise to an angle of 90 degree,
keep it open for 8 seconds and close the valve.
④
Check whether there is air leakage at all connection parts of pipes.
⑤
Push the top rod of T-branch valve by hexagon wrench to expel
air.
⑥
Repeat the third and fifth steps.
⑦
Open the stop and T-branch valve with a hexagon wrench to make
the unit operate.
⑧
No leakage is allowed, please check all the piping connection
parts. You must test the leakage, generally, it can be tested by soap
water.
(8)Electrical connection
①
Unscrew the screw, take off the control panel cover from
the unit.
②
Cooling type: connect the wire to the related connection
point on the panel and connect the signal connection plug.
Remarks: yellow and green cord should be connected to
connection point with
mark.
③
Fasten the fixture of wire to control panel.
④
Screw up the control panel cover to its original place.
(9)Test running
①
Make sure that the pipes and wires are connected.
②
Make sure that both the liquid valve and gas
valve on the side are completely open.
The connection of power source
¾
Connect the wire to independent power
source socket.
¾
Preparation of remote control.
¾
Run the air-conditioner in cooling
operation mode for 30 minutes or longer.
Performance evaluation
¾
Test the out and in air temperature.
¾
Make sure that the temperature difference
between the out and in air is greater than
8
o
C.
(10)Items of attention
①
Fix the machine firmly, otherwise it will produce noise and vibration.
②
Install the outdoor unit where it will not disturb your neighbor.
19
Summary of Contents for ASW-H09A4/SAR1DI
Page 1: ...FOR Split Wall Mounted Series R410a DC Inverter ASW H09A4 SAR1DI ASW H12A4 SAR1DI 2008 ...
Page 6: ...Remote Controller Instructions 4 ...
Page 7: ...5 ...
Page 8: ...6 ...
Page 9: ...7 ...
Page 10: ...8 ...
Page 11: ...9 ...
Page 12: ...10 ...
Page 13: ...11 ...
Page 14: ...12 ...
Page 15: ...13 ...
Page 16: ...14 ...
Page 17: ...15 ...
Page 42: ...Exploded Pictures 1 Indoor unit exploded picture ASW H09A4 SAR1DI 40 ...
Page 44: ... 2 Outdoor unit exploded picture ASW H09A4 SAR1DI 42 ...
Page 46: ... 3 Indoor unit exploded picture ASW H12A4 SAR1DI 44 ...
Page 48: ... 2 Outdoor unit exploded picture ASW H12A4 SAR1DI 46 ...