R32
Split Type - Air Source Heat Pump 20220105
96
Clear all
records
On the History Errors page, press the
【
OK
】
, and a prompt box will pop up. Use the
【
left
】
or the
【
right
】
to select "Yes" or "No". Select "No" and press the
【
OK
】
or directly press the
【
BACK
】
to return to the History Errors display interface, select "Yes" and press the
【
OK
】
to
delete all historical fault records and return to the historical fault display interface . (All module faults
are displayed in the same window, clear all faults)
3.3.6.5 Set New Password
On the repair page, by pressing the
【
up
】
or the
【
down
】
, the item indicated by the arrow
indicates the current selection, select " Set New Password ", and press the
【
OK
】
to enter the
password modification interface.
/
Interface
Interface
modification
By pressing the
【
left
】
or the
【
right
】
to select the digit to be entered for the password, the
reversed digit indicates the current selection.
Select the password value to be input by pressing the
【
up
】
or the
【
down
】
(input range: 0-
9 and A-Z).
After entering the 4-digit password, press the
【
OK
】
to verify and compare it with the password
stored in the host. If the password is the same, enter the Enter New Password page.
3.3.6.6 Factory Para Recovery
On the commissioning page, by pressing the
【
up
】
or the
【
down
】
the item indicated by the
arrow indicates the current selection, select "restore factory settings", enter the loading default
parameter interface through the
【
OK
】
, and press
【
OK
】
to start Recovery, and the loading is
successful as shown in the figure below.