The Operator Panel - Overview
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 9
0
i
C
9
8
7
6
5
4
3
2
1
Testing
Fire Brig. Disabled
System Fault
Alarms Disabled
Fire Brig. Fault
!
!
!
!
Alarms Fault
System Fault
Steady yellow light when a
system
fault within the operating zone of the operator panel is present.
Alarms Fault
Yellow light when a fault is detected on one or more Fire Alarm Devices (FAD). The
Fault
indicator
will also have a yellow light. Blinking (not accepted) / Steady (accepted).
Testing
Steady yellow light when one or more detection zones within the operation zone of the operator
panel have been manually set to the test state.
Fire Brig. Disabled
Steady yellow light when the signal to Fire Alarm Routing Equipment (FARE)
has been disabled. The
Function Disabled
indicator has also a steady yellow light.
Fire Brig. Fault
Yellow light when a fault is detected on Fire Alarm Routing Equipment (FARE). The
Fault
indicator
will also have a yellow light. Blinking (not accepted) / Steady (accepted).
Alarms Disabled
Steady yellow light when one or more Fire Alarm Devices are disabled. The
Function Disabled
indicator has also a steady yellow light.
2.2.2 The Operator Section (lower)