Service Commands
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 97
Step
Actions to be taken
Display Indication
4
To select OUTPUT TEST, press 2.
SERVICE
19:23
OUTPUT TEST
1 MANUAL TEST ON
2 MANUAL TEST OFF
SERVICE
19:23
OUTPUT TEST
1 MANUAL TEST ON
2 MANUAL TEST OFF
5
To select MANUAL TEST OFF, press 2.
SERVICE
19:23
MANUAL TEST OFF
1 FIRE ALARM DEVICES
2 FIRE PROTECTION EQUIPMENT
3 FIRE WARNING ROUTING EQUIPMENT
4 OTHER OUTPUTS
SERVICE
19:23
MANUAL TEST OFF
1 FIRE ALARM DEVICES
2 FIRE PROTECTION EQUIPMENT
3 FIRE WARNING ROUTING EQUIPMENT
4 OTHER OUTPUTS
6
To select FIRE ALARM DEVICES, press 1.
SERVICE
19:23
MANUAL TEST OFF>FAD
Alarm Zone name:
ATTIC
GROUND FLOOR
HOUSE
SERVICE
19:23
MANUAL TEST OFF>FAD
Alarm Zone name:
ATTIC
GROUND FLOOR
HOUSE
7
Use the keyboard to enter text into the input box
-
OR
,- as shown in this example:
To select the Alarm Zone Name, press
then scroll downwards by pressing
9
YZ
or move up again by pressing
6
PQR
SERVICE
19:23
MANUAL TEST OFF>FAD
Alarm Zone name:
ATTIC
GROUND FLOOR
HOUSE
SERVICE
19:23
MANUAL TEST OFF>FAD
Alarm Zone name:
ATTIC
GROUND FLOOR
HOUSE
8
To accept the selected Alarm Zone and
terminate the test, press
SERVICE
19:23
MANUAL TEST OFF
1 FIRE ALARM DEVICES
2 FIRE PROTECTION EQUIPMENT
3 FIRE WARNING ROUTING EQUIPMENT
4 OTHER OUTPUTS
SERVICE
19:23
MANUAL TEST OFF
1 FIRE ALARM DEVICES
2 FIRE PROTECTION EQUIPMENT
3 FIRE WARNING ROUTING EQUIPMENT
4 OTHER OUTPUTS
www.ukpanels.com