Operation Mode
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. E, 021105,
Autronica Fire and Security AS
Page 27
In the display, a detection zone with its outputs delayed is indicated by
a
✹
in front of the zone text. The time for the first delayed action is also
displayed.
1 OFFICES
2 CANTEEN
3
✹
WORKSHOP
FIRE ALARMS
19:23
Total: 3
Delayed Action Indication (
✹
)
2: ACTIVATE 4: SHOW SUPPR. INFO
FIRST DELAYED OUTPUTS ACTIVATES 19:40
After pressing the ENTER button ( ) and selecting the delayed
action zone, you can;
•
press Action Digit 1 to
show the points in alarm
•
press Action Digit 2 to
activate the alarm
or
press Action Digit 4 to
prolong the delay
.
FIRE ALARMS
19:23
Total: 3
1: SHOW POINTS
2: ACTIVATE 4: PROLONG DELAY
Action Digits
DELAYED OUTPUTS ACTIVATES 19:40
1 OFFICES
2 CANTEEN
3
✹
WORKSHOP
Figure 3-8: Delayed Action detection zone - indication
www.ukpanels.com