Current output 4...20 mA
Factory setting
Measuring range scaled
P =
VMR =
ASP =
AEP=
System pressure
Final value of the measuring range
Analogue start point [ASP2]
Analogue end point [AEP2]
In the measuring range, the output signal is between 4 and 20 mA�
It is also indicated:
• System pressure above [AEP2]: 20���20�5 mA
• System pressure below [ASP2]: 4���3�8 mA
• Fault indication according to Namur: 21�5 mA�
4.4 IO-Link
General information
This unit has an IO-Link communication interface which requires an IO-Link-
capable module (IO-Link master) for operation�
The IO-Link interface enables direct access to the process and diagnostic data
and provides the possibility to set the parameters of the unit during operation�
In addition communication is possible via a point-to-point connection with a USB
adapter cable�
Further information about IO-Link at www�autosen�com�