8.2 Explanation of the menu
8.2.1 Explanation of the menu level 1
SPx / rPx Upper / lower limit value for system pressure at which OUTx switches with
hysteresis setting� Prerequisite: OUTx setting is [Hno] or [Hnc]�
FHx / FLx Upper / lower limit value for system pressure at which OUTx switches with
window setting� Prerequisite: OUTx setting is [Fno] or [Fnc]�
ASP2
Analogue start point for system pressure: measured value at which 4 mA / 0 V
are provided� Prerequisite: OUT2 setting is [I] or [U]�
AEP2
Analogue end point for system pressure: measured value at which
20 mA / 10 V are provided� Prerequisite: OUT2 setting is [I] or [U]�
EF
Extended functions / opening of menu level 2�
8.2.2 Explanation of the menu level 2
rES
Restore factory setting�
ou1
Output function for OUT1:
• Switching signal for the pressure limit values: hysteresis function [H ��] or
window function [F ��], either normally open [� no] or normally closed [� nc]�
ou2
Output function for OUT2:
• Switching signal for the pressure limit values: hysteresis function [H ��] or
window function [F ��], either normally open [� no] or normally closed [� nc]�
• Analogue signal for the current system pressure: 4���20 mA [I] or 0���10 V [U]�
dS1 / dS2 Switching delay for OUT1 / OUT2�
dr1 / dr2
Switch-off delay for OUT1 / OUT2�
uni
Standard unit of measurement for system pressure (display):
[bAr] / [mbar] / [MPA] / [kPA] / [PSI] / [inHG] / [iH2O] / [mmWS] �
P-n
Output logic: pnp / npn�
Lo
Minimum value memory for system pressure�
Hi
Maximum value memory for system pressure�
dAP
Damping of the switch point�
dAA
Damping of the analogue output�
Prerequisite: OUT2 setting is [I] or [U]�
coF
Zero-point calibration�
coLr
Assignment of the display colours "red" and "green" within the measuring
range�
cFH / cFL Upper / lower value for colour change� Parameter only active after selection of
a freely definable colour window in the coLr parameter: [r-cF] or [G-cF]�
diS
Update rate and orientation of the display�