19
UK
► Select [FLx] and set the lower limit value�
FLx is always lower than FHx� The unit only accepts values which are lower
than the value for FHx�
9.3.4 Scaling of the analogue value
► Select [ASP2] and set the value at which 4 mA / 0 V is provided�
► Select [AEP2] and set the value at which 20 mA / 10 V is provided�
Minimum distance between ASP2 and AEP2 = 20 % of the measuring
span (scaling factor 5)�
9.4 User settings (optional)
9.4.1 Set delay for the switching outputs
[dS1] / [dS2] = switching delay for OUT1 / OUT2�
[dr1] / [dr2] = reset delay for OUT1 / OUT2�
► Select [dS1], [dS2], [dr1] or [dr2] and set a value between 0 and 50 s (at
0 the delay time is not active)�
For this unit the parameters [dSx] and [drx] for the set and reset
points are designed strictly to the VDMA guideline�
9.4.2 Set output logic for the switching outputs
► Select [P-n] and set [PnP] or [nPn]�
9.4.3 Set damping for the switching signal
► Select [dAP] and set the damping constant in seconds
(value
T
: 63 %); setting range 0�000���4�000 s�
Damping affects [dAP] the switch point / process data flow (IO-Link
communication) and the display�
9.4.4 Damping for analogue output
► Select [dAA] and set the damping constant (rise time 10���90 %) in
seconds; setting range 0�000���4�000 s�
Damping [dAA] only affects the analogue output / analogue signal
path�
9.4.5 Zero-point calibration
► Select [coF] and set a value between -5 % and 5 % of the final value of
the measuring range� The internal measured value "0" is shifted by this
value�