G-14
PSQ Series
Parameter Setting
※
After entering parameter 1/2 group, if there is no additional key input for 60 sec, it maintains previous setting value and it returns to RUN mode.
※
Press the
,
key to set the setting value.
※
After entering parameter 1/2 group, press the
M
key for over 2 sec to return to RUN mode.
※
When pressing the
M
key once returning RUN mode from parameter 1 group, 2 group within 2 sec, it enters the previous parameter group.
※
Some parameters are activated/deactivated according to the setting of other parameters. Refer to the description of each parameter.
Parameter Group
Parameter 1 group
Parameter name
Setting range
Description
Factory
default
OUT1
OUT1 operation
mode
EASY
HYsM
WIN
AUTO
fOUT
Easy
Hysteresis
Window comparison
Auto sensitivity setting
Forced output control
Select OUT1 operation mode.
※
When setting OUT1 operation mode as auto sensitivity setting mode [
AUTO
] or
forced output control mode [
fOUT
], OUT2 operation mode is set automatically
same as the setting value of OUT1 operation mode.
EASY
OUT2
OUT2 operation
mode
OFF
EASY
HYsM
WIN
OFF
Easy
Hysteresis
Window comparison
Select OUT2 operation mode.
OFF
I/O
※
1
Analog output/
External input
A-V
A-C
SHFT
ZERO
HOLD
Analog voltage output
Analog current output
Auto shift
Remote zero
Hold
Select analog output/external input operation mode.
Auto shift:
When reference pressure of the pressure sensor changes, It
corrects present pressure to reference pressure and by moving
detection level as much as fluctuation level.
Remote zero: I
t is the same function as auto shift but remote zero
makes the measured pressure as 0 forcibly.
Hold: The function to hold present value (PV) and control output while
signal is input.
※
When OUT1 operation mode is set as [
fOUT
] or applied pressure
is higher/lower than the display pressure range, auto shift [
SHFT
],
remote zero [
ZERO
] functions are not available.
A-V
ShOT
※
1
Auto shift
applied terminal
OUT1
OUT2
ALL
OUT1
OUT2
OUT1 & OUT2
Select auto shift applied terminal.
※
Appears when Analog output/External input is [
SHFT
].
OUT1
ZeOT
※
1
Remote zero
applied terminal
OUT1
OUT2
ALL
OUT1
OUT2
OUT1 & OUT2
Select remote zero applied terminal.
※
Appears when analog output/external input is [
ZERO
].
OUT1
NoNC
Output type
OUT1
OUT2
NO
Normally Open
OFF
※
Appears when OUT2 operation mode is [
OFF
].
NC
Normally Closed OFF
1O2O
Normally Open
Normally Open
※
Appears when OUT1 operation mode is [
AUTO
],
or OUT2 operation mode is [
HYsM
], [
WIN
].
1O2C
Normally Closed
Normally Open
1C2O
Normally Closed
Normally Open
1C2C
Normally Closed
Normally Closed
NO
SPD
Response time
@5
,
5
,
10
,
25
,
50
,
100
,
250
,
500
,
1000
,
5000
It can prevent control output from chattering by changing response time.
※
If the response time is getting longer, the detection will be more stable
but present value (PV) might be different from the real pressure
value.
@5
CLOR
PV display color
R-ON
G-ON
RED
GREN
Normal: Green / Output: Red
Normal: Red / Output: Green
Fixed red
Fixed green
Select the present value (PV) display and the color linked output.
R-ON
DISP
Color linked
output
OUT1
OUT2
ALL
OUT1
OUT2
OUT1 & OUT2
Select the color linked output.
※
Appears when OUT2 operation mode is not [
OFF
] and PV display color
is set as [
R-ON
] and [
G-ON
].
OUT1
UNIT
Display unit
KPA
MPA
KGF
BAR
PSI
MMHG
INHG
H2O
kPa
MPa
kgf/cm
2
bar
psi
mmHg
inHg
mmH
2
O
Select the display unit.
※
For using
mmH
2
O unit, multiply display value by 100.
KPA
※
1: Appears only in NPN or PNP open collector analog output or external input model.