 Installation

 Proper Usage

 

 

Caution

 

 

Caution

1. Pressure port is divided as standard and option

  specification. Therefore, make sure use commercially 

  available one touch fitting. 

    ● Pneumatic type: Rc1/8, R1/8, NPT1/8

  ● Fluid type: Rc1/8, R1/8, R1/4, NPT1/4, 9/16-18UNF

2. 

U

se a spanner (pneumatic type: 12mm, fluid type: 17mm)

    at the metal part of the unit in order not to overload on 

    the body when connecting one touch fitting.

3. Two different brackets are provided for pneumatic type 

and one different brackets are provided for fluid type. 

Select proper one with considering your application  

environments.

4. 

At first, please unscrew hexagon wrench bolt and 

    assemble the bracket on this unit by fixing hexagon the 

    wrench bolt.

 

    

In this case, tightening torque of hexagon wrench

    

should be max. 3N.m. It may cause mechanical

    

problems.

ᆞ 

12-24VDC model, power supply should be insulated and 

limited voltage/current or Class 2, SELV power supply 

device.

 Do not insert any sharp or pointed object into pressure 

port. Failure to follow these instructions may result in 

malfunction and damage to the sensor.

Be sure that this unit must avoid direct touch with water,

 

 

oil, thinner, etc. 

5. PSQ Series has panel bracket (PSO-B02),

  front cover (PSO-P01) are sold separately.  

  When mounting the unit on panel, please follow the  

  below figure. 

The tightening torque of one touch fitting should be 

max. 10N.m. It may cause mechanical problems.

Front cover

(PSO-P01)

Mounting panel

   (panel thickness 0.8~3.5mm)

Panel bracket 

(PSO-B02)

Body

(PSQ)

SMPS

 

+

 

F.G.

-

Do not use the product in preparation time (within 3 sec).

   

  

for operating after power-on.

When using switching mode power supply, frame ground 

   

  

(F.G.) terminal of power supply should be grounded.

Avoid wiring with power line or high voltage line. 

  It may cause malfunction by noise. 

When moving this unit from cold place to warm place, 

  please remove the humidity on the cover.

Do not press the setting button with sharp or pointed 

  object.

Do not apply a tensile strength in excess of 30N to the

  cables or connector.

This unit may be used in the following environment.

 ①

 

Indoors

 ②

 

Altitude max. 2,000m

 ③

 

Pollution degree 3

 ④

 

Installation category II

 

PSQ Series is for sensing of non corrosive gas. 

Do not use this product at corrosive gas or flammable 

gas, etc.

12mm

spanner

17mm

spanner

<

Pneumatic type

>

<

Fluid type

>

Bracket C

Spring washer

Hexagon wrench 

bolt (M3×6) 

Bracket A

Bracket B

<

Pneumatic type

>

<

Fluid type

>

  When using separate installation set

6. Do not pull the cable with a tensile strength of 30N or over.

Body

(PSQ)

Front cover 

(PSO-P02)

Front panel bracket

(PSO-B04)

Rear panel bracket 

(PSO-B04)

Mounting panel

(panel thickness: 0.5 to 7mm) 

  When using integrated installation set

<

Pneumatic/Fulid type

>

<

Pneumatic type

>

Summary of Contents for PSQ Series

Page 1: ...60 0 133322kPa 101 32472kPa Features Pressure Conversion Chart to from Pa kPa MPa kgf cm2 mmHg mmH2O psi bar inHg 1Pa 1 0 001 0 000001 0 000010197 0 007501 0 101972 0 000145038 0 00001 0 0002953 1kPa 1000 000 1 0 001 0 010197 7 500617 101 971626 0 145038 0 01 0 2953 1MPa 1000000 1000 1 10 197162 7500 61683 101971 626 145 038243 10 295 299875 1kgf cm2 98066 5 98 0665 0 098067 1 735 55924 10000 0005...

Page 2: ...0ms 500ms 1 000ms 5 000ms Protection circuit Output short over current protection circuit Analog output 3 Voltage output Output voltage 1 5VDCᜡ 2 5 F S Linear max 1 F S Resolution 1 2 000 Output impedance approx 240Ω Response time 50ms Current output Output current DC4 20mA 2 5 F S Linear max 1 F S Resolution 1 2 000 Output impedance approx 100kΩ Response time 50ms External input 3 Auto shift Remo...

Page 3: ...y for over 4 sec to enter parameter 2 group Setting mode Press the M key to select the setting items Press the M key for over 2 sec to return RUN mode 5 key RUN mode Press the key to set preset value of output operation mode Press the M keys to set key lock unlock Press the keys to adjust zero point Press the M keys to set peak hold Preset value setting mode Press the key to increase decrease sett...

Page 4: ...ss 0 5 to 7mm 31 0 0 4 When N units are installed in series 31 0 0 4 31 N 3 5 N 1 Min 55 Integrated installation set Pneumatic Fluid type Separate installation set Pneumatic type 28 2 40 30 40 42 35 26 3 20 25 8 Rear panel bracket Front panel bracket Front cover PSO P01 Front cover PSO P02 Panel cut out Front Rear pael bracket set PSO B04 Panel bracket PSO B02 Panel cut out 6 75 7 37 41 34 2 42 39...

Page 5: ...own V blue 0V black OUT1 white OUT2 12 24VDC orange analog output external input Load Load RUN mode Preset value setting Zero point adjustment Parameter 2 group Key lock High Low peak hold for over 1 sec It sets reference pressure to the current atmospheric pressure as zero for over 1 sec for over 1 sec Output short over current protection circuit Output short over current protection circuit Outpu...

Page 6: ...ld The function to hold present value PV and control output while signal is input When OUT1 operation mode is set as fOUT or applied pressure is higher lower than the display pressure range auto shift SHFT remote zero ZERO functions are not available A V ShOT 1 Auto shift applied terminal OUT1 OUT2 ALL OUT1 OUT2 OUT1 OUT2 Select auto shift applied terminal Appears when Analog output External input...

Page 7: ... Only checking parameters 0000 sOUT Control output switching NPN PNP NPN PNP Select type of control output NPN HYS Hysteresis for easy mode 1 to 1 1 1 1 1 1 1 1 Bar type Min 1ea Max 8ea Set the hysteresis for easy mode Rated pressure range Hysteresis per 1 Bar 100 0 to 100 0kPa 0 1kPa 100 0 to 1 000kPa 1kPa Appears when OUT1 or OUT2 operation mode is easy mode Although the display unit is changed ...

Page 8: ...setting by output operation mode Output operation mode Preset Setting range Factory default 100 0 to 100 0kPa 100 to 1 000kPa EASY Easy P Pressure detection level Min display pressure P Max display pressure 05 0 0500 HYsM Hysteresis ST Pressure detection level Min display pressure ST Max display pressure 05 0 0500 HYS Hysteresis level Min display pressure HYS ST 5 0 0000 WIN Window com parison LO ...

Page 9: ...tput voltage or current and external input auto shift remote zero hold are not available at the same time Analog output A V Analog voltage output A C Analog current output External input SHFT Auto shift ZERO Remote zero HOLD Hold Preset setting by external input mode External input mode Preset Setting range Factory default SHFT Auto shift ShIN Auto shift correction value Min preset setting value S...

Page 10: ...1 ST2 Hysteresis is fixed as Min display interval The pressure detection level SET is shown in the below formula ST1 ST2 2 SET Pressure 1 Min display interval 1 1 1 ST1 ST2 SET SET ST1 ST2 OUT1 N O OUT2 N O OUT1 N C OUT2 N C ST2 SET ST1 ON OFF ON OFF ON OFF ON OFF Time Time Time Time Time Forced output control mode fOUT RUN mode fOUT Regardless of setting value it maintains comparison output OFF a...

Page 11: ...COPY Slave unit PV display arbitrary value SV display OK M Master Slave brown V blue 0V black OUT1 black OUT1 white OUT2 white OUT2 Auto Shift Remote Zero Hold input Output mode change OUT1 operation mode There are 4 kinds of control output mode in order to realize the various pressure detection Hysteresis mode HYsM When needed to change hysteresis for detecting pressure Window comparison output m...

Page 12: ...the SV display part in RUN mode There are 3 types displaying SV STD displaying unit UNIT none OFF RESET This function is to reset all parameters as factory default except control output SV to prevent wrong settings or difficult operation Password This function is to limit parameter settings to check the parameter or to change the parameter settings only for entering the set password 0000 Password ...

Page 13: ...t this unit must avoid direct touch with water oil thinner etc 5 PSQ Series has panel bracket PSO B02 front cover PSO P01 are sold separately When mounting the unit on panel please follow the below figure The tightening torque of one touch fitting should be max 10N m It may cause mechanical problems Front cover PSO P01 Mounting panel panel thickness 0 8 3 5mm Panel bracket PSO B02 Body PSQ SMPS F ...

Reviews: