Functions
ᆞ
Set pressure value for 1VDC output [
A-1V
] and
pressure value for 5VDC output [
A-5V
].
[
A-1V
] setting range: 0% F.S.≤ [
A-1V
]
≤
100% F.S.
[
A-5V
] setting range: 0% F.S.≤ [
A-5V
]
≤ [
A-1V
]
-
10% F.S. or
[
A-1V
]
+
10% F.S.≤ [
A-5V
]
≤100% F.S.
ᆞ
Set pressure value for 4mA output [
A-04
] and
pressure value for 20mA output [
A-20
].
[
A-04
] setting range: 0% F.S.≤ [
A-04
]
≤100% F.S.
[
A-20
] setting range: 0% F.S.≤ [
A-20
]≤ [
A-04
]-10% F.S. or
[
A-04
]
+
10% F.S.≤ [
A-20
]≤100% F.S.
Analog output scale adjustment
Parameter copy
※
This function is for copying parameter settings of Master
to Slave 1:1. Master and Slave should be the same
specification model.
※
1:
ON
: Copies SVs.,
ON-L
: Copies SVs and locks front keys of Slave unit.
※
2: When connecting
Master unit and Slave unit incorrectly,
the PV display of Master unit displays
ERR4
.
Turn OFF the Master unit power and turn ON it.
It displays
REDY
at SV display part.
※
3: The PV display part of
Master displays as orange
color. The PV display part of Slave displays as green
color. When completing copy, the PV display part of
Master and Slave displays the same arbitrary value.
※
4: Connect other Slave units to copy parameters.
※
only for NPN or PNP open collector
analog output or external input type
Set output voltage, output current to the current display
value at 1-5VDC voltage output [
A-V
], DC4-20mA [
A-C
]
current output.
※
1
※
2
※
3
※
4
At Master unit,
Set parameter copy [
COPY
] of
PA 2 group as
ON
or
ON-L
At Master unit,
SV display part:
REDY
Turn OFF the Master unit
Connect Master/Slave units
Turn ON the Master/Slave units
with pressing the
M
key
Turn OFF the Master/Salve units
and disconnect
Master/Slave units
[Master unit]
PV display: arbitrary value
SV display:
COPY
[Slave unit]
PV display: arbitrary value
SV display:
OK
M
[Master]
[Slave]
(brown) +V
(blue) 0V
(black) OUT1 (black) OUT1
(white) OUT2
(white) OUT2
Auto Shift/Remote Zero/Hold input
Output mode change
OUT1 operation mode
There are 4 kinds of control output mode in order to realize
the various pressure detection.
• Hysteresis mode [
HYsM
]
: When needed to change hysteresis for detecting pressure.
• Window comparison output mode [
WIN
]
: When needed to detect pressure in certain area.
• Automatic sensitivity setting mode [
AUTO
]
: When needed to set detection sensitivity automatically at
proper position.
• Forced output control mode [
fOUT
]
: When needed to display pressure with remaining
comparison output OFF regardless of setting value.
OUT2 operation mode
Select control output mode between two types or
OFF
.
In case of OUT1 operation mode, select automatic sensi
-
tivity setting mode [
AUTO
] or forced output control mode
[
fOUT
]. OUT2 operation mode setting is inactive.
• Hysteresis mode [
HYsM
]
: When needed to change hysteresis for detecting pressure.
• Window comparison output mode [
WIN
]
: When needed to detect pressure in certain area.
• OFF [
OFF
]
※
Only for NPN or PNP open collector
analog output or external input type
Auto Shift [
SHFT
], Remote Zero [
ZERO
]
Hold [
HOLD
]
ᆞ
Deleting correction value
:
Press the
+
keys for over 1 sec to delete
set
auto
shift correction.
The function to hold PV and control output while signal is input.
When reference pressure of the pressure sensor changes,
apply auto shift or remote zero digital input. It corrects
present pressure to reference pressure and by moving
detection level as much as fluctuation level. In case of
remote zero, it is the same function as auto shift but
remote zero makes the measured pressure as 0 forcibly.
When changing analog output and external input setting,
auto shift correction value [
ShIN
], remote zero correction
value [
ZeIN
] are also reset as 0.
ᆞ
Setting correction value
: Press the
, key to set SV manually or
apply
0VDC
to orange cable over 1ms.
When selecting analog output/external input [
I/O
] of
parameter 1 group as
[
SHFT
] or [
ZERO
], press the
M
key to select control output
at
[
ShOT
], [
ZeOT
] to be with
correction value.