background image

G-19

Compact, Dual LCD Display Digital Pressure Sensor

SENSORS

CONTROLLERS

MOTION DEVICES

SOFTWARE

(A)

Photoelectric 

Sensors

(B)

Fiber Optic

Sensors

(C)

LiDAR

(D)

Door/Area

Sensors

(E)

Vision

Sensors

(F)

Proximity

Sensors 

(G)

Pressure

Sensors 

(H)

Rotary

Encoders 

(I)

Connectors/

Connector Cables/

Sensor Distribution 

Boxes/ Sockets

 Functions

Set pressure value for 1VDC output [

A-1V

] and 

  pressure value for 5VDC output [

A-5V

].

  [

A-1V

] setting range: 0% F.S.≤ [

A-1V

]

 

 

100% F.S.

  [

A-5V

] setting range: 0% F.S.≤ [

A-5V

]

 

≤ [

A-1V

]

 

-

10% F.S. or

                                  

 

[

A-1V

]

 

+

10% F.S.≤ [

A-5V

]

 

≤100% F.S.

Set pressure value for 4mA output [

A-04

] and

  pressure value for 20mA output [

A-20

].

  [

A-04

] setting range: 0% F.S.≤ [

A-04

]

 

≤100% F.S.

  [

A-20

] setting range: 0% F.S.≤ [

A-20

]≤ [

A-04

]-10% F.S. or

                                  

 

[

A-04

]

 

+

10% F.S.≤ [

A-20

]≤100% F.S.

 

Analog output scale adjustment

 Parameter copy

This function is for copying parameter settings of Master 

    to Slave 1:1. Master and Slave should be the same 

    specification model. 

1:  

ON

: Copies SVs.,  

ON-L

: Copies SVs and locks front keys of Slave unit. 

 

2:  When connecting 

Master unit and Slave unit incorrectly, 

the PV display of Master unit displays 

ERR4

        Turn OFF the Master unit power and turn ON it.  

It displays 

REDY

 at SV display part. 

3:  The PV display part of 

Master displays as orange 

color. The PV display part of Slave displays as green 

color.  When completing copy, the PV display part of 

       

 

Master and Slave displays the same arbitrary value.

4: Connect other Slave units to copy parameters.

only for NPN or PNP open collector

   

 

analog output or external input type

Set output voltage, output current to the current display 

value at 1-5VDC voltage output [

A-V

], DC4-20mA [

A-C

current output.

1

2

3

4

At Master unit, 

Set parameter copy [

COPY

] of 

PA 2 group as 

ON

 or 

ON-L

At Master unit,

SV display part: 

REDY

Turn OFF the Master unit

Connect Master/Slave units

Turn ON the Master/Slave units 

with pressing the 

M

 

key

Turn OFF the Master/Salve units 

and disconnect 

Master/Slave units

 [Master unit]

PV display: arbitrary value

SV display: 

COPY

 [Slave unit]

PV display: arbitrary value

SV display: 

OK

M

   

   

[Master]

[Slave]

 

 

(brown) +V

(blue) 0V

(black) OUT1 (black) OUT1

(white) OUT2

(white) OUT2

 Auto Shift/Remote Zero/Hold input

 Output  mode  change                                                                                         

 

 OUT1 operation mode

There are 4 kinds of control output mode in order to realize 

the various pressure detection.  

• Hysteresis mode [

HYsM

]

  : When needed to change hysteresis for detecting pressure.

• Window comparison output mode [

WIN

]

  : When needed to detect pressure in certain area.

• Automatic sensitivity setting mode [

AUTO

  : When needed to set detection sensitivity  automatically at

    proper position.

• Forced output control mode [

fOUT

  : When needed to display pressure with remaining 

    comparison output OFF regardless of setting value.

 OUT2 operation mode

Select control output mode between two types or 

OFF

In case of OUT1 operation mode, select automatic sensi

-

tivity setting mode [

AUTO

] or forced output control mode 

[

fOUT

]. OUT2 operation mode setting is inactive.

• Hysteresis mode [

HYsM

]

  : When needed to change hysteresis for detecting pressure.  

• Window comparison output mode [

WIN

]

  : When needed to detect pressure in certain area. 

• OFF [

OFF

]

Only for NPN or PNP open collector

   

 

analog output or external input type

 

 Auto Shift [

SHFT

], Remote Zero [

ZERO

]

 

 Hold [

HOLD

]

Deleting correction value

   : 

Press the 

 

+

 

 keys for over 1 sec to delete 

set 

auto

     

 

 

shift correction.

The function to hold PV and control output while signal is input.

When reference pressure of the pressure sensor changes, 

apply auto shift or remote zero digital input. It corrects 

present pressure to reference pressure and by moving 

detection level as much as fluctuation level. In case of 

remote zero, it is the same function as auto shift but 

remote zero makes the measured pressure as 0 forcibly. 

When changing analog output and external input setting, 

auto shift correction value [

ShIN

], remote zero correction 

value [

ZeIN

] are also reset as 0.

Setting correction value

  : Press the 

,   key to set SV manually or 

apply 

0VDC

    to orange cable over 1ms. 

     When selecting analog output/external input [

I/O

] of 

parameter 1 group as 

[

SHFT

] or [

ZERO

], press the 

M

 

key to select control output 

at 

[

ShOT

], [

ZeOT

] to be with 

correction value. 

Summary of Contents for PSQ Series

Page 1: ...60 0 133322kPa 101 32472kPa Features Pressure Conversion Chart to from Pa kPa MPa kgf cm2 mmHg mmH2O psi bar inHg 1Pa 1 0 001 0 000001 0 000010197 0 007501 0 101972 0 000145038 0 00001 0 0002953 1kPa 1000 000 1 0 001 0 010197 7 500617 101 971626 0 145038 0 01 0 2953 1MPa 1000000 1000 1 10 197162 7500 61683 101971 626 145 038243 10 295 299875 1kgf cm2 98066 5 98 0665 0 098067 1 735 55924 10000 0005...

Page 2: ...0ms 500ms 1 000ms 5 000ms Protection circuit Output short over current protection circuit Analog output 3 Voltage output Output voltage 1 5VDCᜡ 2 5 F S Linear max 1 F S Resolution 1 2 000 Output impedance approx 240Ω Response time 50ms Current output Output current DC4 20mA 2 5 F S Linear max 1 F S Resolution 1 2 000 Output impedance approx 100kΩ Response time 50ms External input 3 Auto shift Remo...

Page 3: ...y for over 4 sec to enter parameter 2 group Setting mode Press the M key to select the setting items Press the M key for over 2 sec to return RUN mode 5 key RUN mode Press the key to set preset value of output operation mode Press the M keys to set key lock unlock Press the keys to adjust zero point Press the M keys to set peak hold Preset value setting mode Press the key to increase decrease sett...

Page 4: ...ss 0 5 to 7mm 31 0 0 4 When N units are installed in series 31 0 0 4 31 N 3 5 N 1 Min 55 Integrated installation set Pneumatic Fluid type Separate installation set Pneumatic type 28 2 40 30 40 42 35 26 3 20 25 8 Rear panel bracket Front panel bracket Front cover PSO P01 Front cover PSO P02 Panel cut out Front Rear pael bracket set PSO B04 Panel bracket PSO B02 Panel cut out 6 75 7 37 41 34 2 42 39...

Page 5: ...own V blue 0V black OUT1 white OUT2 12 24VDC orange analog output external input Load Load RUN mode Preset value setting Zero point adjustment Parameter 2 group Key lock High Low peak hold for over 1 sec It sets reference pressure to the current atmospheric pressure as zero for over 1 sec for over 1 sec Output short over current protection circuit Output short over current protection circuit Outpu...

Page 6: ...ld The function to hold present value PV and control output while signal is input When OUT1 operation mode is set as fOUT or applied pressure is higher lower than the display pressure range auto shift SHFT remote zero ZERO functions are not available A V ShOT 1 Auto shift applied terminal OUT1 OUT2 ALL OUT1 OUT2 OUT1 OUT2 Select auto shift applied terminal Appears when Analog output External input...

Page 7: ... Only checking parameters 0000 sOUT Control output switching NPN PNP NPN PNP Select type of control output NPN HYS Hysteresis for easy mode 1 to 1 1 1 1 1 1 1 1 Bar type Min 1ea Max 8ea Set the hysteresis for easy mode Rated pressure range Hysteresis per 1 Bar 100 0 to 100 0kPa 0 1kPa 100 0 to 1 000kPa 1kPa Appears when OUT1 or OUT2 operation mode is easy mode Although the display unit is changed ...

Page 8: ...setting by output operation mode Output operation mode Preset Setting range Factory default 100 0 to 100 0kPa 100 to 1 000kPa EASY Easy P Pressure detection level Min display pressure P Max display pressure 05 0 0500 HYsM Hysteresis ST Pressure detection level Min display pressure ST Max display pressure 05 0 0500 HYS Hysteresis level Min display pressure HYS ST 5 0 0000 WIN Window com parison LO ...

Page 9: ...tput voltage or current and external input auto shift remote zero hold are not available at the same time Analog output A V Analog voltage output A C Analog current output External input SHFT Auto shift ZERO Remote zero HOLD Hold Preset setting by external input mode External input mode Preset Setting range Factory default SHFT Auto shift ShIN Auto shift correction value Min preset setting value S...

Page 10: ...1 ST2 Hysteresis is fixed as Min display interval The pressure detection level SET is shown in the below formula ST1 ST2 2 SET Pressure 1 Min display interval 1 1 1 ST1 ST2 SET SET ST1 ST2 OUT1 N O OUT2 N O OUT1 N C OUT2 N C ST2 SET ST1 ON OFF ON OFF ON OFF ON OFF Time Time Time Time Time Forced output control mode fOUT RUN mode fOUT Regardless of setting value it maintains comparison output OFF a...

Page 11: ...COPY Slave unit PV display arbitrary value SV display OK M Master Slave brown V blue 0V black OUT1 black OUT1 white OUT2 white OUT2 Auto Shift Remote Zero Hold input Output mode change OUT1 operation mode There are 4 kinds of control output mode in order to realize the various pressure detection Hysteresis mode HYsM When needed to change hysteresis for detecting pressure Window comparison output m...

Page 12: ...the SV display part in RUN mode There are 3 types displaying SV STD displaying unit UNIT none OFF RESET This function is to reset all parameters as factory default except control output SV to prevent wrong settings or difficult operation Password This function is to limit parameter settings to check the parameter or to change the parameter settings only for entering the set password 0000 Password ...

Page 13: ...t this unit must avoid direct touch with water oil thinner etc 5 PSQ Series has panel bracket PSO B02 front cover PSO P01 are sold separately When mounting the unit on panel please follow the below figure The tightening torque of one touch fitting should be max 10N m It may cause mechanical problems Front cover PSO P01 Mounting panel panel thickness 0 8 3 5mm Panel bracket PSO B02 Body PSQ SMPS F ...

Reviews: