2 Modbus Mapping Table
24
© Copyright Reserved Autonics Co., Ltd.
No(Address)
Parameter
Description
Set range
Unit
Factory
default
400229(00E4)
RSW.T
Communication response waiting
time
5 to 99:
5
to
99
ms
20
400230(00E5)
COMW
Communication write
enable/disable
0:
EnA
1:
DIsA
-
EnA
400225 to
400250
Reserved
2.4.6
Parameter 5 group[Func: 03/06/16, RW: R/W]
No(Address)
Parameter Description
Set range
Unit
Factory default
400251(00FA)
MtSV
Number of Multi-SVs
0:
1
1:
2
2:
4
EA
1
400252(00FB)
DI-K
Front DI input key function
0 :
OFF
1 :
AT
2 :
STOP
3 :
AL.RE
-
STOP
400253(00FC)
DI-1
DI-1input terminal function 0:
OFF
1 :
STOP
2:
AlRE
3:
MAN
4:
MtSV
5:
ReSV
-
OFF
400254(00FD)
DI-2
DI-2 input terminal function
-
400255(00FE)
ReSV
Remote SV
0 :
OFF
1 :
ON
OFF
400256(00FF)
RInB
Remote SV low-limit value
correction
-999 to 999 :
-999
to
0999
-1999 to 9999 :
`9(9
to
99(9
0000
400257(0100)
RSPN
Remote SV gradient
correction
0.100 to 5.000 :
)100
to
%000
1.000
400258(0101)
BAR
Bar graph
0:
OFF
1:
OUT1
(standard)
0:
OFF
1:
OUT1
2:
OUT2
3:
ALL
(heating/cooling)
OUT1
400259(0102)
Manual control, initial MV
0: AUTO 1: PrMV
-
ALL
400260(0103)
ItMV
Manual control, preset MV
00)0
to
10)0
(standard)
`0)0
to
10)0
(heating/cooling)
%
AUTO
400261(0104)
PrMV
Sensor error, MV
00)0
to
10)0
(standard)
`0)0
to
10)0
(heating/cooling)
%
00)0
400262(0105)
ErMV
Control stop, MV
00)0
to
10)0
(standard)
`0)0
to
10)0
(heating/cooling)
%
00)0
400263(0106)
StMV
Control stop, Alarm output 0: CONT 1: OFF
-
00)0
400264(0107)
StAL
User group
0: STND 1: HIGH
-
CONT
400265(0108)
USER
Parameter initialization
0:
NO
1:
YES
-
STND
400266(0109)
INIT
SV set group lock
0:
OFF
1:
ON
-
NO
400267(010A)
LcSV
Parameter 1 group lock
0:
OFF
1:
ON
-
OFF
400268(010B)
LcP1
Parameter 2 group lock
0:
OFF
1:
ON
-
OFF
400269(010C)
LcP2
Parameter 3 group lock
0:
OFF
1:
ON
-
OFF
400270(010D)
LcP3
Parameter 4 group lock
0:
OFF
1:
ON
-
OFF
400271(010E)
LcP4
Parameter 5 group lock
0:
OFF
1:
ON
-
OFF
400272(010F)
LcP5
Password
0000
: OFF
0002
to
9999
: Password set range
(
※
0001
: password for reading)
-
OFF
400273 to 400300 Reserved
Summary of Contents for KPN Series
Page 2: ...Preface 2 Copyright Reserved Autonics Co Ltd...
Page 6: ...Communication protocol 6 Copyright Reserved Autonics Co Ltd...
Page 8: ...Table of Contents 8 Copyright Reserved Autonics Co Ltd...
Page 16: ...1 Modbus RTU protocol 16 Copyright Reserved Autonics Co Ltd...
Page 25: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 25...