2 Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd.
23
2.4.5
Parameter 4 group[Func: 03/06/16, RW: R/W]
No(Address)
Parameter
Description
Set range
Unit
Factory
default
400201(00C8)
AL-1
Alarm output1 mode
0:
OFF
1:
DVCC
2:
]]DV
3:
]DVC
4:
CDV]
5:
PVCC
6:
]]PV
7:
LBA
8:
SBA
9:
HBA
-
DVCC
400202(00C9)
AL!T
Alarm output1 option
0:
AL-A
1:
AL-B
2:
AL-C
3:
AL-D
4:
AL-E
5:
AL-F
-
AL-A
400203(00CA)
A!HY
Alarm output1 hysteresis
1 to 100:
001
to
100
(temperature H,
analog)
1 to 1000:
00)1
to
10)0
(temperature L)
Digit
001
400204(00CB)
A!N
Alarm output1 N.O./N.C.
0:
NO
1 :
NC
-
NO
400205(00CC)
A!ON
Alarm output1 ON delay time
0 to 3600:
0000
to
3600
sec.
0000
400206(00CD)
A!OF
Alarm output1 OFF delay time
0 to 3600:
0000
to
3600
sec.
0000
400207(00CE)
AL-2
Alarm output2 mode
0: OFF 1: DVCC 2: ]]DV 3: ]DVC
4: CDV] 5: PVCC 6: ]]PV 7: LBA
8: SBA 9: HBA
-
]]DV
400208(00CF)
AL@T
Alarm output2 option/type
0:
AL-A
1:
AL-B
2:
AL-C
3:
AL-D
4: AL-E 5: AL-F
-
AL-A
400209(00D0)
A@HY
Alarm output2 hysteresis
1 to 100:
001
to
100
(temperature H,
analog)
1 to 1000:
00)1
to
10)0
(temperature L)
Digit
001
400210(00D1)
A@N
Alarm output2 N.O./N.C.
0:
NO
1:
NC
-
NO
400211(00D2)
A@ON
Alarm output2 ON delay time
0 to 3600:
0000
to
3600
sec.
0000
400212(00D3)
A@OF
Alarm output2 OFF delay time
0 to 3600:
0000
to
3600
sec.
0000
400213(00D4)
AL-3
Alarm output3 mode
0:
OFF
1:
DVCC
2:
]]DV
3:
]DVC
4:
CDV]
5:
PVCC
6:
]]PV
7:
LBA
8:
SBA
9:
HBA
-
LBA
400214(00D5)
AL#T
Alarm output3 option/type
0:
AL-A
1:
AL-B
2:
AL-C
3:
AL-D
4:
AL-E
5:
AL-F
-
AL-A
400215(00D6)
A#HY
Alarm output3 hysteresis
1 to 100:
001
to
100
(temperature H,
analog)
1 to 1000:
00)1
to
10)0
(temperature L)
Digit
001
400216(00D7)
A#N
Alarm output3 N.O./N.C.
0:
NO
1:
NC
-
NO
400217(00D8)
A#ON
Alarm output3 ON delay time
0 to 3600:
0000
to
3600
sec.
0000
400218(00D9)
A#OF
Alarm output3 OFF delay time
0 to 3600:
0000
to
3600
sec.
0000
400219(00DA)
LBaT
LBA monitoring time
0 to 9999:
0000
to
9999
sec.
0000
400220(00DB)
Reserved
400221(00DC)
LBaB
LBA detection band
1 to 9999:
001
to
999
(temperature H)
1 to 9999:
00)1
to
99(9
(temperature L)
1 to 9999:
0001
to
9999
(analog)
℃
/
℉
%F.S
003
00#0
0)20
400222(00DD)
AO-M
Analog trans. output value
0:
PV
1:
SV
2:
H-MV
3:
C-MV
-
PV
400223(00DE)
FS-L
PV trans. output low-limit value
F.S
℃
/
℉
/-
-200
400224(00DF)
FS-H
PV trans. output high-limit value F.S
1350
400225(00E0)
ADRS
Communication address
1 to 127:
01
to
127
-
01
400226(00E1)
BPS
Communication speed
0:
24
1:
48
2:
96
3:
192
4:
384
X100bps
96
400227(00E2)
PRTY
Communication parity bit
0:
NONE
1:
EVEN
2:
ODD
-
NONE
400228(00E3)
STP
Communication stop bit
0:
1
1:
2
Bit
2
Summary of Contents for KPN Series
Page 2: ...Preface 2 Copyright Reserved Autonics Co Ltd...
Page 6: ...Communication protocol 6 Copyright Reserved Autonics Co Ltd...
Page 8: ...Table of Contents 8 Copyright Reserved Autonics Co Ltd...
Page 16: ...1 Modbus RTU protocol 16 Copyright Reserved Autonics Co Ltd...
Page 25: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 25...