Autonics KPN Series User Manual For Communication Download Page 14

1 Modbus RTU protocol 

 

 

14 

 

© Copyright Reserved Autonics Co., Ltd. 

1.6

 

Preset Multiple Registers(Func16–10H) 

Write the Binary data of Holding Registers (4X reference) consecutively in Slave device.

 

(1)

 

Query(Master) 

Slave 
Address 

Function 

Starting 
  Address 

No. of Register 

Byte Count

 

Data 

Data 

Error Check 
(CRC16) 

High 

Low 

High 

Low 

High 

Low 

High 

Low 

Low 

High 

1Byte 

1Byte 

1Byte 

1Byte 

1Byte 

1Byte 

1Byte 

1Byte 

1Byte 

1Byte 

1Byte 

1Byte 

1Byte 

 

(2)

 

Response(Slave) 

Slave Address  Function 

Starting Address 

No. of Register 

Error Check(CRC16) 

High 

Low 

High 

Low 

Low 

High 

1Byte 

1Byte 

1Byte 

1Byte 

1Byte 

1Byte 

1Byte 

1Byte 

 

If write

 “10(

A H

)” 

in common to the range of Holding Register

 

400001(0000 

H

)

 to 

400

002(0001

 

H

on Slave side 

(

Address

 

17)

 from Master side.

 

 

Query(Master) 

Slave   
Address 

Function 

Starting 
Address 

No. of Register 

Byte Count

 

Data 

Data 

Error Check 
(CRC16) 

High 

Low 

High 

Low 

High 

Low 

High 

Low 

Low 

High 

11 H 

10 H 

00 H 

00 H 

00 H 

02 H 

04 H 

00 H 

0A H 

00 H 

0A H 

## H 

## H 

 

Response(Slave) 

Slave Address  Function 

Starting Address 

No. of Register 

Error Check(CRC16) 

High 

Low 

High 

Low 

Low 

High 

11 H 

10 H 

00 H 

00 H 

00 H 

02 H 

## H 

## H 

Please use the Single Register Write function rather than Multi Register Write function if 
you use the slave(device) connecting with external devices such as PLC, Graphic Panel, 
except in the case of download that presets the minimum/maximum or basic value of 
parameter by Input specifications in PC Loader Program. 

 

 

CRC16 

CRC16 

Summary of Contents for KPN Series

Page 1: ...re Controllers KPN Series ACM E 0301 AB Thank you for purchasing an Autonics product This user manual contains information about the product and its proper use and should be kept in a place where it w...

Page 2: ...Preface 2 Copyright Reserved Autonics Co Ltd...

Page 3: ...ng Autonics product Please familiarize yourself with the information contained in the Safety Precautions section before using this product This user manual contains information about the product and i...

Page 4: ...r reproduced in either part or whole without permission A user manual is not provided as part of the product package Visit our web site www autonics com to download a copy The manual s content may var...

Page 5: ...Communication protocol Copyright Reserved Autonics Co Ltd 5 Communication protocol KPN Series is supported to Modbus RTU protocol However it does not support broadcast commands...

Page 6: ...Communication protocol 6 Copyright Reserved Autonics Co Ltd...

Page 7: ...10H 14 1 7 Exception Response Error Code 15 2 Modbus Mapping Table 17 2 1 Read Coils Func01 Write Single Coil Func05 17 2 2 Read Discrete Inputs Func02 17 2 3 Read Input Registers Func04 18 2 4 Read H...

Page 8: ...Table of Contents 8 Copyright Reserved Autonics Co Ltd...

Page 9: ...1Byte 1Byte 1Byte 1Byte 1Byte If read the output status ON 1 OFF 0 of 10EA within coil 000001 0000 H to 000010 0009 H on Slave side Address 17 from Master side Query Master Slave Address Function Star...

Page 10: ...yte 1Byte 1Byte 1Byte If read the input status ON 1 OFF 0 of 10EA range 100001 0000 H to 100010 0009 H in the Slave side Address 17 from the Master side Query Master Slave Address Function Starting Ad...

Page 11: ...igh Low High Low High Low Low High 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte If read the values of 2EA from Holding Register 400001 0000 H to 400002 0001 H in Slave Address 17...

Page 12: ...CRC16 Low High 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte If read the values of 2EA range from Input Register 300001 0000 H to 300002 0001 H on Slave side Address 17 from Master side Query Master...

Page 13: ...sponse Slave Slave Address Function Register Address Preset Data Error Check CRC16 High Low High Low Low High 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte If write 10 A H to Holding Register 400001...

Page 14: ...in common to the range of Holding Register 400001 0000 H to 400002 0001 H on Slave side Address 17 from Master side Query Master Slave Address Function Starting Address No of Register Byte Count Data...

Page 15: ...data is inconsistent with transmittable address from the device ILLRGAL DATA VALUE Exception Code 03 H The number of queried data are inconsistent with the numbers of transmittable transferable data f...

Page 16: ...1 Modbus RTU protocol 16 Copyright Reserved Autonics Co Ltd...

Page 17: ...100003 0002 lamp 0 OFF 1 ON 100004 0003 OUT1 lamp Control output1 display lamp 0 OFF 1 ON 100005 0004 OUT2 lamp Control output2 display lamp 0 OFF 1 ON 100006 0005 AT lamp Auto tuning RUNlamp 0 OFF 1...

Page 18: ...eserved 300117 0074 Reserved 300118 0075 Coil status start Address 0000 300119 0076 Coli status Quantity 0 300120 0077 Input status start Address 0000 300121 0078 Input status Quantity 0 300122 0079 H...

Page 19: ...splay lamp 0 OFF 1 ON Bit A AL3 lamp Alarm output3 display lamp 0 OFF 1 ON Bit B MAN lamp Manual control display lamp 0 OFF 1 ON Bit C DI 1 input DI 1 input status 0 OFF 1 ON Bit D DI 2 input DI 2 inp...

Page 20: ...ss Parameter Description Set range Unit Factory default 400051 0032 R S Control output RUN STOP 0 RUN 1 STOP RUN 400052 0033 SV N Multi SV No 0 SV 0 1 SV 1 2 SV 2 3 SV 3 SV 0 400053 0034 CT A Heater c...

Page 21: ...0 05 0 400110 006D hHYS Heating hysteresis 1 to 100 001 to 100 temperature H analog 1 to 1000 00 1 to 10 0 temperature L Digit 002 400111 006E hOST Heating OFF offset 0 to 100 000 to 100 temperature...

Page 22: ...MAvF Input digital filter 1 to 1200 00 1 to 12 0 sec 00 1 400161 00A0 L SV SV low limit set value Input low limit value L SC to H SV 1Digit F S 200 00 0 400162 00A1 H SV SV high limit set value L SV...

Page 23: ...0 0000 to 3600 sec 0000 400212 00D3 A OF Alarm output2 OFF delay time 0 to 3600 0000 to 3600 sec 0000 400213 00D4 AL 3 Alarm output3 mode 0 OFF 1 DVCC 2 DV 3 DVC 4 CDV 5 PVCC 6 PV 7 LBA 8 SBA 9 HBA LB...

Page 24: ...100 to 5 000 100 to 000 1 000 400258 0101 BAR Bar graph 0 OFF 1 OUT1 standard 0 OFF 1 OUT1 2 OUT2 3 ALL heating cooling OUT1 400259 0102 Manual control initial MV 0 AUTO 1 PrMV ALL 400260 0103 ItMV Ma...

Page 25: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 25...

Page 26: ...Dimensions or specifications on this manual are subject to change and some models may be discontinued without notice...

Reviews: