1 Modbus RTU protocol
12
© Copyright Reserved Autonics Co., Ltd.
1.4
Read Input Registers(Func04–04H)
Read the Binary data of Input Registers(3X reference) in Slave device.
(1)
Query(Master)
Slave Address Function
Starting Address
No. of Points
Error Check(CRC16)
High
Low
High
Low
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
(2)
Response(Slave)
Slave Address Function
Byte Count
Data
Data
Data
Error Check(CRC16)
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
If read the values of 2EA range from Input Register 300001(0000 H) to 300002(0001 H)
on Slave side(Address 17) from Master side.
Query(Master)
Slave Address Function
Starting Address
No. of Points
Error Check(CRC16)
High
Low
High
Low
Low
High
11 H
04 H
00 H
00 H
00 H
02 H
## H
## H
If the values of
300001(0000
H
) and 300002(0001
H
) are respectively “10(
A H
)” and
“20(14
H
)”
on Slave side are respectively
.
Response(Slave)
Slave Address Function
Byte Count
Data
Data
Error Check(CRC16)
High
Low
High
Low
Low
High
11 H
04 H
04 H
00 H
0A H
00 H
14 H
## H
## H
CRC16
CRC16
Summary of Contents for KPN Series
Page 2: ...Preface 2 Copyright Reserved Autonics Co Ltd...
Page 6: ...Communication protocol 6 Copyright Reserved Autonics Co Ltd...
Page 8: ...Table of Contents 8 Copyright Reserved Autonics Co Ltd...
Page 16: ...1 Modbus RTU protocol 16 Copyright Reserved Autonics Co Ltd...
Page 25: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 25...