Autonics KPN Series User Manual For Communication Download Page 22

2 Modbus Mapping Table 

 

 

22 

 

© Copyright Reserved Autonics Co., Ltd. 

2.4.4

 

Parameter 3 group[Func: 03/06/16, RW: R/W] 

No(Address) 

Parameter  Description 

Set range 

Unit 

Factory default 

400151(0096) 

IN-T 

Input type 

Refer to the input type table.   

TCk1 

400152(0097) 

UNIT 

Sensor temperature unit  0: 

?C

   1: 

?F

 

?C 

400153(0098) 

L-RG 

Analog low-limit input 

value 

Min. range to   

H-RG

 - F.S10% 

Digit 

00)0 

400154(0099) 

H-RG 

Analog high-limit input 

value 

L-RG

+F.S10% to Max. range 

Digit 

10)0 

400155(009A) 

DOT 

Scale value decimal 

point position 

0:

 0

   1: 

)0   

2: 

)00

   3: 

)000

 

)0 

400156(009B) 

L-SC 

Scale low-limit display 

value 

F.S 

00)0 

400157(009C) 

H-SC 

Scale high-limit display 

value 

F.S 

10)0 

400158(009D) 

dUNT 

Front display unit 

0: 

?C

   1: 

?F   

2: 

?/O

   3: 

OFF

 

?C 

400159(009E) 

IN-B 

Input correction 

-999 to 999: 

-999

 to 

0999

 

-1999 to 9999: 

`9(9

 to 

99(9

 

Digit 

0000 

400160(009F) 

MAvF 

Input digital filter 

1 to 1200: 

00)1

 to 

12)0

 

sec. 

00)1 

400161(00A0) 

L-SV 

SV low-limit set value 

Input low-limit value (

L-SC

) to 

H-SV-1

Digit 

/

 

%F.S 

-200 

00)0 

400162(00A1) 

H-SV 

SV high-limit set value 

L-SV

+

1

Digit to input high-limit value (

H-SC

/

 

%F.S 

1350 

10)0 

400163(00A2) 

O-FT 

Control output operation 

mode 

Standard 

0: 

HEAT 

    1: 

COOL

 

HEAT 

HEAT 

Heating/Cooling 0: 

HEAT

    1: 

COOL

    2: 

H-C

 

H-C 

H-C 

400164(00A3) 

C-MD 

Temperature control 

mode 

Standard 

0: 

PID

    1: 

ONOF

 

PID 

PID 

Heating/Cooling 

0: 

pP

   1: 

Pon   

2: 

OnP 

   

3: 

OnON

 

pP 

pP 

400165(00A4) 

ATT 

Auto-tuning mode 

0: 

TUN1

   1:  

TUN2

 

TUN1 

400166(00A5) 

OUT1 

OUT1 control output 

0: 

RLY 

  1: 

SSR

   2: 

CURR

(1 output type) 

RLY 

0: 

SSR

   1: 

CURR

(2 output type) 

SSR 

400167(00A6) 

O!MA 

OUT1 current output 

range 

0: 

4-20

    1: 

0-20

 

4-20 

400168(00A7) 

OUT2 

OUT2 control output   

0: 

SSR

   1: 

CURR

 

SSR 

400169(00A8) 

O@MA 

OUT2 current output 

range 

0: 

4-20

    1: 

0-20

 

4-20 

400170(00A8) 

H-T 

Heating, control time 

1 to 1200: 

00)1

 to 

12)0

 

sec. 

02)0 

400171(00AA) 

C-T 

Cooling, control time 

1 to 1200: 

00)1

 to 

12)0

 

sec. 

02)0 

400172 to 

400200 

Reserved 

 

 

 

 

Summary of Contents for KPN Series

Page 1: ...re Controllers KPN Series ACM E 0301 AB Thank you for purchasing an Autonics product This user manual contains information about the product and its proper use and should be kept in a place where it w...

Page 2: ...Preface 2 Copyright Reserved Autonics Co Ltd...

Page 3: ...ng Autonics product Please familiarize yourself with the information contained in the Safety Precautions section before using this product This user manual contains information about the product and i...

Page 4: ...r reproduced in either part or whole without permission A user manual is not provided as part of the product package Visit our web site www autonics com to download a copy The manual s content may var...

Page 5: ...Communication protocol Copyright Reserved Autonics Co Ltd 5 Communication protocol KPN Series is supported to Modbus RTU protocol However it does not support broadcast commands...

Page 6: ...Communication protocol 6 Copyright Reserved Autonics Co Ltd...

Page 7: ...10H 14 1 7 Exception Response Error Code 15 2 Modbus Mapping Table 17 2 1 Read Coils Func01 Write Single Coil Func05 17 2 2 Read Discrete Inputs Func02 17 2 3 Read Input Registers Func04 18 2 4 Read H...

Page 8: ...Table of Contents 8 Copyright Reserved Autonics Co Ltd...

Page 9: ...1Byte 1Byte 1Byte 1Byte 1Byte If read the output status ON 1 OFF 0 of 10EA within coil 000001 0000 H to 000010 0009 H on Slave side Address 17 from Master side Query Master Slave Address Function Star...

Page 10: ...yte 1Byte 1Byte 1Byte If read the input status ON 1 OFF 0 of 10EA range 100001 0000 H to 100010 0009 H in the Slave side Address 17 from the Master side Query Master Slave Address Function Starting Ad...

Page 11: ...igh Low High Low High Low Low High 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte If read the values of 2EA from Holding Register 400001 0000 H to 400002 0001 H in Slave Address 17...

Page 12: ...CRC16 Low High 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte If read the values of 2EA range from Input Register 300001 0000 H to 300002 0001 H on Slave side Address 17 from Master side Query Master...

Page 13: ...sponse Slave Slave Address Function Register Address Preset Data Error Check CRC16 High Low High Low Low High 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte If write 10 A H to Holding Register 400001...

Page 14: ...in common to the range of Holding Register 400001 0000 H to 400002 0001 H on Slave side Address 17 from Master side Query Master Slave Address Function Starting Address No of Register Byte Count Data...

Page 15: ...data is inconsistent with transmittable address from the device ILLRGAL DATA VALUE Exception Code 03 H The number of queried data are inconsistent with the numbers of transmittable transferable data f...

Page 16: ...1 Modbus RTU protocol 16 Copyright Reserved Autonics Co Ltd...

Page 17: ...100003 0002 lamp 0 OFF 1 ON 100004 0003 OUT1 lamp Control output1 display lamp 0 OFF 1 ON 100005 0004 OUT2 lamp Control output2 display lamp 0 OFF 1 ON 100006 0005 AT lamp Auto tuning RUNlamp 0 OFF 1...

Page 18: ...eserved 300117 0074 Reserved 300118 0075 Coil status start Address 0000 300119 0076 Coli status Quantity 0 300120 0077 Input status start Address 0000 300121 0078 Input status Quantity 0 300122 0079 H...

Page 19: ...splay lamp 0 OFF 1 ON Bit A AL3 lamp Alarm output3 display lamp 0 OFF 1 ON Bit B MAN lamp Manual control display lamp 0 OFF 1 ON Bit C DI 1 input DI 1 input status 0 OFF 1 ON Bit D DI 2 input DI 2 inp...

Page 20: ...ss Parameter Description Set range Unit Factory default 400051 0032 R S Control output RUN STOP 0 RUN 1 STOP RUN 400052 0033 SV N Multi SV No 0 SV 0 1 SV 1 2 SV 2 3 SV 3 SV 0 400053 0034 CT A Heater c...

Page 21: ...0 05 0 400110 006D hHYS Heating hysteresis 1 to 100 001 to 100 temperature H analog 1 to 1000 00 1 to 10 0 temperature L Digit 002 400111 006E hOST Heating OFF offset 0 to 100 000 to 100 temperature...

Page 22: ...MAvF Input digital filter 1 to 1200 00 1 to 12 0 sec 00 1 400161 00A0 L SV SV low limit set value Input low limit value L SC to H SV 1Digit F S 200 00 0 400162 00A1 H SV SV high limit set value L SV...

Page 23: ...0 0000 to 3600 sec 0000 400212 00D3 A OF Alarm output2 OFF delay time 0 to 3600 0000 to 3600 sec 0000 400213 00D4 AL 3 Alarm output3 mode 0 OFF 1 DVCC 2 DV 3 DVC 4 CDV 5 PVCC 6 PV 7 LBA 8 SBA 9 HBA LB...

Page 24: ...100 to 5 000 100 to 000 1 000 400258 0101 BAR Bar graph 0 OFF 1 OUT1 standard 0 OFF 1 OUT1 2 OUT2 3 ALL heating cooling OUT1 400259 0102 Manual control initial MV 0 AUTO 1 PrMV ALL 400260 0103 ItMV Ma...

Page 25: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 25...

Page 26: ...Dimensions or specifications on this manual are subject to change and some models may be discontinued without notice...

Reviews: