1 Modbus RTU protocol
© Copyright Reserved Autonics Co., Ltd.
15
1.7
Exception Response-Error Code
If an error occurs, send a response command and transmit each Exception Code after
set(1) the highest-level bit of received command(Function).
Slave Address F80 H Exception Code
Error Check(CRC16)
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
ILLEGAL FUNCTION(Exception Code: 01 H): A command that is not supported.
ILLEGAL DATA ADDRESS(Exception Code: 02 H): Starting address of queried data
is inconsistent with transmittable address from the device.
ILLRGAL DATA VALUE(Exception Code: 03 H): The number of queried data are
inconsistent with the numbers of transmittable (transferable) data from the device.
SLAVE DEVICE FAILURE(Exception Code: 04 H): Not properly completed the
queried command (order).
Read the output status of non-existing coil 001001(03E8 H) [ON: 1, OFF: 0] on Slave
side(Address 17) from Master side.
Query (Master)
Slave Address Function
Starting Address
No. of Points
Error Check(CRC
16
)
High
Low
High
Low
Low
High
11 H
01 H
03 H
E8 H
00 H
01 H
## H
## H
Response (Slave)
Slave Address Function
+
80
H
Exception Code
Error Check(CRC16)
Low
High
11 H
81 H
02 H
## H
## H
CRC16
Summary of Contents for KPN Series
Page 2: ...Preface 2 Copyright Reserved Autonics Co Ltd...
Page 6: ...Communication protocol 6 Copyright Reserved Autonics Co Ltd...
Page 8: ...Table of Contents 8 Copyright Reserved Autonics Co Ltd...
Page 16: ...1 Modbus RTU protocol 16 Copyright Reserved Autonics Co Ltd...
Page 25: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 25...