8 Timer Mode
© Copyright Reserved Autonics Co., Ltd.
73
(6)
When setting value 1(PRESET 1) is greater than setting value 2(PRESET 2),
In case of OND[
OND
], OND.1[
ONd1
], OND.2[
ONd2
] output mode,
UP mode: Timer setting value 1 (PRESET 1) is greater than setting value 2 (PRESET 2),
OUT 1 output does not turn ON.
DOWN mode: Timer setting value 1 (PRESET 1) is greater than setting value2 (PRESET 2),
OUT1 output does not turn ON. The setting value 1(PRESET 1) is same
as setting value 2 (PRESET 2), OUT1 output turns ON immediately when
applied start signal.
1)
OND
(Signal On Delay) output mode
2)
ONd1
(Signal ON Delay 1) output mode
3)
ONd2
(Signal On Delay 2) output mode