7 Counter Mode
54
© Copyright Reserved Autonics Co., Ltd.
7.6
Prescale
This function is to set and display calculated unit for actual length, liquid, position, etc. It is called
“prescale value” for measured length, liquid, or position, etc per 1 pulse. For example, when
moving L, the desired length to be measured, and P, the number of pulses per 1 revolution of a
rotary encoder, occurs, prescale value is L/P.
Positioning control by counter and encoder
[ Diameter (D) of pulley connected with encoder= 22mm,
the number of pulses by 1 rotation of encoder=1,000]
Prescale value =
π
×
Diameter
(
D
)
of
pulley
The
number
of
pulses
by
1
rotaiton
of
encoder
=
3.1416 ×22
1000
= 0.069mm/pulse
Set decimal point [
DP
] as [
-----.-
], prescale decimal point [
sCDP
] as [
---.---
], prescale
value [
SCL
] as [
0.069
] at function setting mode. It is available to control conveyer position by
0.1mm unit.