7 Counter Mode
© Copyright Reserved Autonics Co., Ltd.
47
Input
mode
Counting chart
Up/
Down-C
[
UD-C
]
※
When connecting encoder output A, B phase with counter input, INA, INB, set input
mode [
InM
] as phase different input [
UD-C
] for counter operation.
※
: over min. signal width,
: over than 1/2 of min. signal width.
If the signal is smaller than these width, it may cause counting error (±1)
※
The meaning of "H", "L"
Input method
Character
Voltage input
(PNP)
No-voltage input
(NPN)
H
5-30VDC
Short
L
0-2VDC
Open
※
Min. signal width by counting speed (1cps = 1Hz)
Counting speed
Min. signal width
1cps
500ms
30cps
16.7ms
1kcps
0.5ms
5kcps
0.1ms
10kcps
0.05ms