8 Timer Mode
60
© Copyright Reserved Autonics Co., Ltd.
Output
mode
Time chart
FLK.2
[
FLk2
]
Flicker 2 (Power Hold)
Hold output
1) Time starts when INA signal turns ON and the display
value at the moment when power is off is memorized.
2) When INA signal is ON: Power ON Time Start is operated.
RESET OFF Time Start is operated.
3) Control output operates as retained output.
4) Control output will be reversed when it reaches to setting
time. (At the initial start, OUT2 control output is OFF).
5) In case of using the contact output, min. setting time must
be set over 100ms.
One-shot output
1) Time starts when INA signal turns ON and the display
value at the moment when power is off is memorized.
2) When INA signal is ON: Power ON Time Start is operated.
RESET OFF Time Start is operated.
3) Control output operates as one-shot output.
4) In case of using the contact output, min. setting time must
be set over 100ms.
※
Power RESET: There is no memory protection. (resets the display value when power is off)
※
Power Hold: There is memory protection. (memorizes the display value at the moment of
power off, indicates the memorized display value when power is resupplied.)
Summary of Contents for CT4S-2P series
Page 1: ...Programmable Counter Timer User Manual CT Series CT Series CT Series ...
Page 2: ...내 ii Copyright Reserved Autonics Co Ltd ...
Page 8: ...Cautions During Use 나 viii Copyright Reserved Autonics Co Ltd ...
Page 16: ...1 Product Overview 16 Copyright Reserved Autonics Co Ltd ...
Page 20: ...3 Communication Specification 20 Copyright Reserved Autonics Co Ltd ...
Page 24: ...4 Dimensions 24 Copyright Reserved Autonics Co Ltd ...
Page 36: ...5 Guide For Connection 36 Copyright Reserved Autonics Co Ltd ...
Page 42: ...6 Basic Operations Counter Timer Communication 42 Copyright Reserved Autonics Co Ltd ...