RS485 Speed Reference
Mem Addr 091AH(42331)
Range: 0.0 to 400.0 Hz
Default Setting: 60.0
• This parameter is used to set the Master Frequency when the AC drive is
controlled by communication interface.
RUN Command
Mem Addr 091BH(42332)
Range: 0 - Stop
Default Setting: 0
1 - Run
Direction Command
Mem Addr 091CH(42333)
Range: 0 - Forward
Default Setting: 0
1 - Reverse
External Fault
Mem Addr 091DH(42334)
Range: 0 - No fault
Default Setting: 0
1 - External fault
Fault Reset
Mem Addr 091EH(42335)
Range: 0 - No action
Default Setting: 0
1 - Fault Reset
JOG Command
Mem Addr 091FH(42336)
Range: 0 - Stop
Default Setting: 0
1 - Jog
9-31
9-30
9-29
9-28
9-27
9-26
GS1 Series AC Drive User Manual
4–49
Chapter 4: AC Drive Parameters
Summary of Contents for GS1-10P2