Multi-Function Input (DI3)
Mem Addr 0302H(40771)
Default Setting: 0
Multi-Function Input (DI4)
Mem Addr 0303H(40772)
Settings for 3-02 and 3-03
Default Setting: 3
Settings
0
External Fault (N.O.)
1
External Fault (N.C.)
2
External Reset
3
Multi-Speed Bit 1
4
Multi-Speed Bit 2
9
Jog
10
External Base Block (N.O.)
11
External Base Block (N.C.)
12
Second Accel/Decel Time
13
Speed Hold
14
Increase Speed
15
Decrease Speed
16
Reset Speed to Zero
99
Input Disable
3-03
3-02
GS1 Series AC Drive User Manual
4–21
Chapter 4: AC Drive Parameters
DI1- RUN/STOP select
"Open" : Stop
"Close" : Run
DI2- FWD/REV select
"Open" : FWD
"Close" : REV
FWD/REV
RUN/STOP
CM
DI2
DI1
3-01: Setting 1
DI1- RUN command
Latching input (N.O.)
Runs when closed
DI3- STOP command
Latching input (N.C.)
Stops when open
DI2
DI3
DI1
CM
STOP
RUN
FWD/REV
DI2- FWD/REV select
"Open" : FWD
"Close" : REV
3-01: Setting 2
}
4-00 must be set to 1.