GS1 Series AC Drive User Manual
4–25
Chapter 4: AC Drive Parameters
Setting 12: Second Accel/Decel Time
Multi-function Input Terminals DI3 and DI4 can be set to select between
Accel/Decel times 1 and 2. Parameters 1-01 and 1-02 set Accel 1 and Decel 1
times. Parameters 1-05 and 1-06 set Accel 2 and Decel 2 times.
Setting 13: Speed Hold
When the Speed Hold command is received, the drive acceleration or
deceleration is stopped and the drive maintains a constant speed.
Frequency
Time
Multi-function
Input Terminal
On
Off
Accel 1
1-01
Accel 2
1-05
Decel 2
1-06
Decel 1
1-02
Maximum Output
Frequency (0-04)
DI3-DI4: Accel/Decel Time 2 Command
"Close": Drive receives Accel/Decel 2 Command signal
DI3-DI4
CM
Accel/Decel 2
Actual Operation Freq.
Time
ON
ON
ON
ON
ON
OFF
Master Freqency
Accel inhibit
Decel inhibit
Decel inhibit
Accel inhibit
Actual Operation Freqency
Freqency
Run
Command
Speed Hold