Chapter 4: AC Drive Parameters
GS1 Series AC Drive User Manual
4–20
Digital Parameters
Source of Operation Command
Mem Addr 0300H(40769)
Default Setting: 0
Settings
0
Operation Determined by Digital Keypad
1
Operation determined by external control
terminals. Keypad STOP is enabled.
2
Operation determined by external control
terminals. Keypad STOP is disabled.
3
Operation determined by RS485 interface.
Keypad STOP is enabled.
4
Operation determined by RS485 interface.
Keypad STOP is disabled.
• This parameter sets the input source for the AC drive operation commands.
• Refer to 3-01 and 3-03 for more details.
Multi-function Input Terminals (DI1-DI2)Mem Addr 0301H(40770)
Default Setting: 0
Settings
0
DI1 - FWD/STOP
DI2 - REV/STOP
1
DI1 - RUN/STOP
DI2 - REV/FWD
2
DI1 - RUN (N.O. latching input)
DI2 - REV/FWD
DI3 - STOP (N.C. latching input)
Note: Multi-function Input Terminals DI1 and DI2 do not have separate parameter
designations. DI1 and DI2 must be used in conjunction with one another to operate two
and three wire control.
3-01
3-00
REV/STOP
FWD/STOP
CM
DI2
DI1
3-01: Setting 0
DI1
DI2
Result
OFF
OFF
STOP
ON
OFF
FWD
OFF
ON
REV
ON
ON
STOP